6-2 Initializing and Saving Data and Removing the Memory Card
NS5 Data Initialize Screen
Page 1 Page 2
6-2-1 Screen Data Area Format
This function formats the PT screen data. Screen data must be formatted if it is corrupted and
cannot start up properly. The data recorded for the operation log, alarm history, data log, and
error log is not initialized when screen data is formatted.
Note Before formatting screen data, check that the screen data has been backed up from the CX-
Designer.
Format the screen data by using operations from the Initialize Data Tab Page in the System
Menu, as follows:
1. Press the Screen Data Area Button.
A confirmation message will be displayed. Press the Yes Button to format the data. Press the
No Button to cancel the initialize function.
2. When the PT has completed formatting screen data, a dialog box will be displayed indicating
that the screen data has finished being formatted.
3. An error message will be displayed if the System Menu is closed while screen data is being
formatted. Always transfer the screen data from the CX-Designer or Memory Card after format-
ting.
Reference
The PT must be restarted after screen data has been transferred.
6-10

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NS5-SQ00 V2 Series and is the answer not in the manual?

Omron NS5-SQ00 V2 Series Specifications

General IconGeneral
BrandOmron
ModelNS5-SQ00 V2 Series
CategoryTouch terminals
LanguageEnglish

Related product manuals