12-1
12-1 Troubleshooting
OMNUC G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
12
Troubleshooting and Maintenance
12-1 Troubleshooting
Preliminary Checks When a Problem Occurs
This section explains the preliminary checks and analytical software required to determine the
cause of a problem if one occurs.
Checking the Power Supply Voltage
 Check the voltage at the power supply input terminals.
Main Circuit Power Supply Input Terminals (L1, L2, L3)
R88D-KN@L-ECT-R (50 to 400 W): Single-phase 100 to 120 VAC (85 to 132 V) 50/60 Hz
R88D-KN@H-ECT-R (100 W to 1.5 kW): Single-phase 200 to 240 VAC (170 to 264 V) 50/60 Hz
R88D-KN@H-ECT-R (750 W to 1.5 kW): 3-phase 200 to 240 VAC (170 to 264 V) 50/60 Hz
(2 kW to 5 kW): 3-phase 200 to 230 VAC (170 to 253 V) 50/60 Hz
R88D-KN@F-ECT-R (750 W to 5 kW): 3-phase 380 to 480 VAC (323 to 528 V) 50/60 Hz
 Control Circuit Power Supply Input Terminals (L1C, L2C)
R88D-KN@L-ECT-R (50 to 400 W): Single-phase 100 to 120 VAC (85 to 132 V) 50/60 Hz
R88D-KN@H-ECT-R (100 W to 1.5 kW): Single-phase 200 to 240 VAC (170 to 264 V) 50/60 Hz
(2 kW to 5 kW): 3-phase 200 to 230 VAC (170 to 253 V) 50/60 Hz
R88D-KN@F-ECT-R (750 W to 5 kW): 24 VDC (21.6 to 26.4 V)
 If the voltage is out of range, there is a risk of operation failure. Be sure that the power supply is
within the specified range.
 Check the voltage of the sequence input power supply (+24 VIN terminal (CN1 pin 7)).
It must be between 11 and 25 VDC.
If the voltage is out of range, there is a risk of operation failure. Be sure that the power supply is
within the specified range.
Checking Whether an Error Has Occurred
 Make an analysis using the 7-segment display on the front of the Servo Drive or using CX-Drive
tools.
When an Error Has Occurred
…
Check the error display (
@@
) and make an analysis based on the error that is indicated.
 When an Error Has Not Occurred
… Make an analysis according to the error conditions.
 In either case, refer to 12-4 Troubleshooting on page 12-13 for details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron OMNUC G5 Series and is the answer not in the manual?

Omron OMNUC G5 Series Specifications

General IconGeneral
BrandOmron
ModelOMNUC G5 Series
CategoryServo Drives
LanguageEnglish

Related product manuals