3-3SectionWiring
45
Note Crimp-type terminals must be used for terminal connections, and the screws
must be tightened securely. Use M3 screws and tighten them to a torque of
0.5 N S m.
6.0 mm max.
6.0 mm max.
M3 screw
Fork Type
Round Type
To minimize output wiring noise, ground the output signal line to the output de-
vice.
3-3-4 Output Wiring Considerations
When wiring outputs, apply the following points to avoid noise interference and
optimize Analog Output Unit performance.
Use shielded twisted-pair cable for external connections.
Route output cables separately from the AC cable, and do not run the Unit’s
cables near a main circuit cable, high voltage cable, or a non-PC load cable.
If there is noise interference from power lines (if, for example, the power supply
is shared with electrical welding devices or electrical discharge machines, or if
there is a high-frequency generation source nearby) install a noise filter at the
power supply output area.
When the power supply to the PC is turned on or off, momentary voltage or
current may be output from the output terminal.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C200H-AD003 and is the answer not in the manual?

Omron SYSMAC C200H-AD003 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C200H-AD003
CategoryI/O Systems
LanguageEnglish

Related product manuals