30. WIRE AND DISCONNECT SIZING
FLEXmax 80
The Charge Controller is a buck type converter with the following properties:
• 80 amp DC output current limit (default setting)
• Listed to operate continuously at 80 amps (40°C/104° F)
With an 80 amp Charge Controller output current limit and PV array output higher than 80 amps o ers
little, if any, current boosting or Maximum Power Point Tracking advantage; in e ect, any excess power
beyond 80 amps is lost.
For NEC* compliance and the Charge Controllers 80 amp output rating / MPPT capabilities, the largest
PV array input must not exceed a rated short-circuit current of 64 amps.
Battery Side of the Controller
All OutBack Power circuit breakers (OBB-XX) are 100% continuous-rated type breakers
The conductors connected to the breakers must have a 125% safety factor applied (i.e., an 80 amp
breaker must have a 100-amp conductor connected when used at its full 80-amp rating)
PV Side of the Controller
UL* requires a 125% safety multiplier (before NEC calculations)
NEC* requires a 125% safety multiplier (after UL calculations).
The 156% safety multiplier is speci c in the NEC* to PV applications only – this dual 125% multiplier
is used because a PV array can produce above its rated output in some conditions.
NEC Compliance
When the 156% safety multiplier is applied, the resulting conductor amperage required is still 100-
amps (1.56 X 64A) and an 80 amp breaker may be used (100% continuous duty rated breaker).
When a PV array is con gured for a higher nominal input voltage (such as 72V PV array), the PV input
conductor can be sized smaller depending on the step-down ratio and the maximum short circuit
current available.
NOTE: The input breaker must also be sized smaller; it cannot be the normal 80 amp with conductor
smaller than #4 AWG. (21.1mm
2
)
* North America

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Outback Power Systems FLEXmax 60 and is the answer not in the manual?

Outback Power Systems FLEXmax 60 Specifications

General IconGeneral
BrandOutback Power Systems
ModelFLEXmax 60
CategoryController
LanguageEnglish

Related product manuals