Troubleshooting
Samsung Electronics 4-57
4-4-12 : Detection of Floating Switch of Indoor Unit's Drain Pump
1. How to check
To release E153 error, you must reset the power of the indoor unit.
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
When checking the
resistance value of both terminals after
disconnecting a floating sensor connector linked
to an indoor unit PCB, is resistance
valve = ∞ ?
Is there a lot of water in the drain plate?
Does Drain pump run
during COMP operation?
Diagnosed as a defective
Floating sensor
No
Drain pump PCB unit
voltage = around AC220V?
Does the water level
in the Drain Pan get lower?
Reset the power of the indoor unit
then check if drain pump operates
(vibrates during operation)
Normal operation
Indoor unit's power reset
after replac ement
Reassembly Floating Sensor Connector
and reset Outdoor Unit pow er
(Indoor unit power reset required)
Normal operation
Diagnosed as a defective
Floating sensor Indoor unit's
power reset after replacement
Replace Drain pump
Replace Drain pump Replace Indoor Unit PCB
Error occurs
×(Operation)
×
(Timer)
(Fan)
(Filter)
×
(Defrost)
t Due to the breakdo wn of a drain pump of the indoor unit, an increase in the water level in the drainage plate
or defective detection sensor
t Refer to how to determine below
Indoor unit display
Criteria
Cause of problem
Outdoor unit display
x x x
(
x x x
:
The address of the error occurred indoor unit)
Float sensor error will be removed
only when the remote controller
for an indoor unit operates

Table of Contents

Other manuals for Samsung AM250FNBFEB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM250FNBFEB/EU and is the answer not in the manual?

Samsung AM250FNBFEB/EU Specifications

General IconGeneral
TypeAir conditioner indoor unit
Multi-split-
Product colorWhite
Gas hose diameter15.88 mm
Liquid hose diameter9.52 mm
Refrigerating mediumR410A
Air conditioner functionsHeating
Heating capacity (nominal)85300 BTU/h
Heating capacity in watts (max)25000 W
Cooling capacity in watts (nominal)- W
Operating temperature (heating) (T-T)-20 - 24 °C
AC input voltage220-240 V
Current (heating)23.1 A
AC input frequency50-60 Hz
Design load (cooling)- kW
Energy efficiency scaleA+ to G
Power consumption (heating) (max)5000 W
Hourly energy consumption (cooling)- kWh
Energy efficiency class (heating) (Average heating season)A+
Indoor unit typeWall-mountable
Indoor unit depth330 mm
Indoor unit width518 mm
Indoor unit height1210 mm
Indoor unit weight104000 g
Indoor units quantity1
Indoor unit package depth426 mm
Indoor unit package width652 mm
Indoor unit package height1289 mm
Indoor unit package weight107000 g
Indoor unit sound power level42 dB
Indoor unit noise level (high speed)61 dB
Outdoor unit noise level- dB

Related product manuals