Power Supply
SICAM TM, Installation 73
DC6-015-2.04, Edition 10.2014
7.5. Fuse Protection
For the fuse protection of the system, miniature circuit breakers 2-pole 2A characteristic C
(standard type: Merlin Gerin C60H 6kA Item No. MER+C60H-C-2A) are recommended. The
number of miniature circuit breakers required depends on the size of the system and
individual requirements. One miniature circuit breaker is recommended for each peripheral
element.
7.6. Primary Mains Unit / Standard Type
See Appendix A, Recommended and tested purchased products