Remedy:CauseMessage
352 You are attempting to select a screen that does not exist
or has been disabled by the function Hide.
353 The minimum value is greater than the maximum value
for variable scales.
Minimum and maximum values are being
confused by OP. To prevent this, enter cor-
rect minimum and maximum values.
354 You are attempting to enter a value in an input field when
the current password level is insufficient for input.
Log on with a higher password level.
355 Entry of this variable has not been configured for the
current PLC mode.
356 A print function has been initiated on the OP. When at-
tempting to print it has been ascertained that the printer is
offline.
Switch the printer online.
Check the connection between the OP and
the printer.
Has the printer been connected to the cor-
rect interface?
357 You are attempting to enter a setpoint that contains an
illegal character.
Enter the value correctly.
358 The OP is currently executing a function which does not
permit use of the OP while it is in progress.
Wait until the function has been completed.
This message may appear in the case of
recipe functions, for example.
365 Incorrect index. A multiplex index is outside the defined
range.
370 Hard copy print-out has been cancelled manually.
371 Print function disabled at present.
372 The function started has been cancelled.
383 For information: transfer of data records completed.
384 Data record required is not on data medium. Check the data record selection parameters
(recipe, data record name, data medium) or
use the Select function to select the data
record.
385 Information message: transfer of data records from OP to
data medium or vice versa has been initiated.
One possible reason is that operation is no
longer possible:
The PLC has not reset the corresponding
386 Information message: transfer of data records from OP to
PLC or vice versa has been initiated.
control and acknowledgment bit, which
deactivates the recipe mailbox lock, in the
interface area.
387 Data record not found. There is no data record relating to the se-
lected recipe on the data medium.
388 Activating selected function.
389 De-activating selected function.
391 No Help text configured. Check configuration.
S