EasyManuals Logo
Home>TECO>Servo Drives>JSDAP Series

TECO JSDAP Series User Manual

TECO JSDAP Series
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #157 background imageLoading...
Page #157 background image
5-71
Setting for the Power of External Regeneration Resistor
When using external regeneration resistor, the power value (Watts) must be set in parameter Cn012.
Parameter Name Default Unit Setting Range Control Mode
Cn012
Watts setting for
External Regeneration
Resistor
0 W 0~10000 ALL
Wiring for External Regeneration Resistor
When external Regeneration Resistor is used, must remove the link between PC and P1 on TB1
Terminal.
Then the resistor should be installed between terminals P and PC.
For safety, use of resistors with thermal protection is recommended.
The thermal switch contact can then be interlocked to disable drive or remove power if necessary.
Refer to connection diagram below:
When installing Regeneration Resistors care must be taken as the resistor absorbs the regeneration
power, and it is possible to generate the high temperatures above 100°C.
Provide the necessary cooling and use appropriate high temperature wires and ensure there has
enough space between regeneration resistor and other materials.

Table of Contents

Other manuals for TECO JSDAP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TECO JSDAP Series and is the answer not in the manual?

TECO JSDAP Series Specifications

General IconGeneral
BrandTECO
ModelJSDAP Series
CategoryServo Drives
LanguageEnglish

Related product manuals