7-4
Parameter
Signal
Name & Function Default Unit
Setting
Range
Control
Mode
Digital input control method selection.
Hn617
Select digital input (12 pins) control method by
external terminal or communication. Convert Binary
code to Hex code for setting this parameter. DI and
binary bits table as below.
Ex. DI-1 is bit 0 and DI-12 is bit 12.
DI-[ ] DI-12
……
…
DI-1
bit 11
……
…
0
Binary code representation :
→” 0 “ Digital input control by external terminal.
→” 1 “ Digital input control by communication.
Set H0000 for Hn617 represent DI-1 ~ DI-12 are
controlled by external terminal and set H0FFF
represent all terminal is controlled by
communication.
Ex. Set DI (1, 3, 6, 10, 12) for communication control
other pins by external terminal;
The corresponding binary code is :[0 1010
0010
0101] convert to Hex code is : [H 0A25]for entering
parameter.
For the setting Bit0 (DI-1) is control by
communication and Bit1 (DI-2) is control by external
terminal ….etc
H0000 X
H0000
│
H0FFF
(HEX)
ALL
Setting digital input status in communication
mode
Hn618
Change Hn618 Hex code for setting digital input
status of communication control mode; Setting
method refer Hn617.
Binary code representation:
“0” : digital input contact OFF
“1” : digital input contact ON
Set H0000 for Hn617 represent DI-1 ~ DI-12 are
controlled by external terminal and set H0FFF
represent all terminal is controlled by
communication.
P.S.)This parameter should co-operate with
Hn617.
H0000 X
H0000
│
H0FFF
(HEX)
ALL