118
4400 Series Installation and Operation Manual – 64527-008
Appendix C – Installation Planning Guide
Installation Planning Guide for 15-100kVA UPS
Standard System: 208/120V Input, 208/120V Output
Rev. 1.6 Page 1 of 3 4400-IPG-208/120v-208/120V
General Mechanical Information
UPS kVA/ kW
Rating
(W x D x H)
Bare (w/ Int Batt.)
Load Heat Loss
Mechanical Clearance for Ventilation
and Maintenance Access
Inches Lbs. kBtu/Hr
Top:
16 in
(406 mm)
Front:
36 in
(900 mm)
Bottom/
Sides/
Back:
0 in.
(0 mm)
Primary AC Input (208/120V 3-Phase / 4-Wire)
Power Demand at 100% Load
Suggested External
Feeder Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
(1) x 4 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 4/0 AWG / (1) 250 kcmil
80 >0.99 224 (239) 400 A
(2) x 2/0 AWG – (1) x 500 kcmil /
(2) x 350 kcmil
380
100 >0.99 280 (295) 500 A
(2) x 4/0 AWG – (1) x 600 kcmil /
(2) x 500 kcmil
380
Bypass AC Input (208/120V 3-Phase / 4-Wire)
Power Demand at 100% Load
Suggested External
Feeder Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
(1) x 6 AWG / (1) x 2 AWG
(1) x 3 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 4/0 / (1) 250 kcmil
80 0.9 222 350 A
(2) x 2/0 AWG – (1) x 400 kcmil /
(2) x 300 kcmil
380
100 0.9 278 450 A
(2) x 3/0 AWG – (1) x 600 kcmil /
(2) x 500 kcmil
380
Battery Backup (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Feeder Breaker
1
Wire Size Per Polarity
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
kVA kWB Amps DC Amps AWG or kcmil at 75º C Temp. Rating Feet
80 79.2 344 A 600 A (2) x 250 kcmil 70
1 – External overcurrent overprotection not needed if battery cabinet(s) are each equipped with an appropriate internal circuit breaker
2 – External feeder cables may change depending on number of battery cabinets placed in parallel.
3 – Feeder ampacity based on worst case temperature conditions and sized to be protected by overcurrent device.