4400 Series Installation and Operation Manual – 64527-008
Appendix C – Installation Planning Guide
TOSHIBA 4400 UPS
Installation Planning Guide for 15-100kVA UPS
Standard System: 208/120V Input, 208/120V Output
Rev. 1.6 Page 1 of 3 4400-IPG-208/120v-208/120V
General Mechanical Information
UPS kVA/ kW
Rating
Dimensions
(W x D x H)
Weight
Bare (w/ Int Batt.)
Approximate Full-
Load Heat Loss
Mechanical Clearance for Ventilation
and Maintenance Access
Inches Lbs. kBtu/Hr
15 kVA/ 13.5 kW
20.12 x 37.4 x 65.06
725 (1015)
4.6
Top:
16 in
(406 mm)
Front:
36 in
(900 mm)
Bottom/
Sides/
Back:
0 in.
(0 mm)
20 kVA/ 22.5 kW
20.12 x 37.4 x 65.06
730 (1020)
6.1
25 kVA/ 22.5 kW
20.12 x 37.4 x 65.06
750 (1035)
7.6
30 kVA/ 27 kW
20.12 x 37.4 x 65.06
760 (1045)
9.1
50 kVA/ 45 kW
32.1 x 37.2 x 73.8
965 (1920)
15.2
80 kVA/ 72 kW
32.1 x 37.2 x 73.6
1550 (N/A)
24.3
100 kVA/ 90 kW
32.1 x 37.2 x 73.6
1650 (N/A)
30.4
Primary AC Input (208/120V 3-Phase / 4-Wire)
Power Demand at 100% Load
Suggested External
Feeder Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
15
>0.99
42 (57)
90 A
(1) x 4 AWG / (1) x 2 AWG
380
20
>0.99
56 (71)
125 A
(1) x 2 AWG / (1) x 2 AWG
380
25
>0.99
70 (85)
150 A
(1) x 2 AWG / (1) x 2 AWG
380
30
>0.99
84 (99)
175 A
(1) x 2 AWG / (1) x 2 AWG
380
50
>0.99
140 (154)
250 A
(1) x 4/0 AWG / (1) 250 kcmil
380
80 >0.99 224 (239) 400 A
(2) x 2/0 AWG (1) x 500 kcmil /
(2) x 350 kcmil
380
100 >0.99 280 (295) 500 A
(2) x 4/0 AWG (1) x 600 kcmil /
(2) x 500 kcmil
380
Bypass AC Input (208/120V 3-Phase / 4-Wire)
Power Demand at 100% Load
Suggested External
Feeder Breaker
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
15
0.9
42
70 A
(1) x 6 AWG / (1) x 2 AWG
380
20
0.9
56
90 A
(1) x 3 AWG / (1) x 2 AWG
380
25
0.9
69
110 A
(1) x 2 AWG / (1) x 2 AWG
380
30
0.9
83
150 A
(1) x 2 AWG / (1) x 2 AWG
380
50
0.9
139
225 A
(1) x 4/0 / (1) 250 kcmil
380
80 0.9 222 350 A
(2) x 2/0 AWG (1) x 400 kcmil /
(2) x 300 kcmil
380
100 0.9 278 450 A
(2) x 3/0 AWG (1) x 600 kcmil /
(2) x 500 kcmil
380
Battery Backup (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Feeder Breaker
1
Suggested Minimum Feeder
Wire Size Per Polarity
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
kVA kWB Amps DC Amps AWG or kcmil at 75º C Temp. Rating Feet
15
14.7
64 A
100 A
(1) x 2 AWG
70
20
19.6
85 A
150 A
(1) x 2 AWG
70
25
24.5
107 A
175 A
(1) x 2 AWG
70
30
29.4
128 A
200 A
(1) x 2 AWG
70
50
49.5
215 A
350 A
(1) x 250 kcmil
70
80 79.2 344 A 600 A (2) x 250 kcmil 70
100
98.9
430 A
700 A
(2) x 350 kcmil
70
1 External overcurrent overprotection not needed if battery cabinet(s) are each equipped with an appropriate internal circuit breaker
2 External feeder cables may change depending on number of battery cabinets placed in parallel.
3 Feeder ampacity based on worst case temperature conditions and sized to be protected by overcurrent device.

Table of Contents

Other manuals for Toshiba 4400 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba 4400 Series and is the answer not in the manual?

Toshiba 4400 Series Specifications

General IconGeneral
BrandToshiba
Model4400 Series
CategoryUPS
LanguageEnglish

Related product manuals