Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Unit Model Number Description
Digit 1 - Manufacturing location
E = Epinal France
Digit 2 - Unit model
I = Airnity
Digit 3 - Unit type
C = Cooling Only
H = Reversible Heat Pump
Digit 4-5-6 Unit size
140
150
170
190
220
250
270
Digit 7 - Efciency level
S = Standard efciency
Digit 8 - Refrigerant
A = R410A Factory Full Refrigerant Charge
8 = R410A Factory Refrigerant Pre-charge
2 = Nitrogen Charge (for units R410A)
B = R454B Factory Full Refrigerant Charge
3 = Nitrogen Charge (for units R454B)
Digit 9 - Unit voltage
E = 400 V - 3 Ph - 50 Hz
Digit 10 - Design Sequence
Digit 11 - Design Sequence
Digit 12 - Auxiliary Heat
X = Without
W = Hot Water Coil
E = Electric Heater
L = Modulating Gas Burner,126 kW
S = Modulating Gas Burner,160 kW
H = Modulating Gas Burner,194 kW
Digit 13 - Gas type
X = Without
1 = Propane Gas
2 = Natural Gas (G20)
3 = Natural Gas (G25)
Digit 14 - Airow conguration
D = Down Supply & Down Return
H = Horizontal Supply & Horizontal Return
I = Down Supply & Horizontal Return
J = Horizontal Supply & Down Return
Digit 15 - Available static pressure
1 = Standard External Static Pressure
2 = High External Static Pressure
Digit 16 - Operating map (cooling mode)
A = Standard Ambient
Digit 17 - Free cooling (Economizer)
X = Without (full recirculation)
A = Temperature Control
B = Enthalpy Control
Digit 18 - Heat Recovery Module
X = Without
R = Congured for Rotary Wheel
B = Congured for Rotary Wheel High Airow
Digit 19 - Dehumidication
X = Without
A = Dehumidication Control
Digit 20 - Outdoor coil treatment
B = Without
E = With
Digit 21 - Indoor coil treatment
1 = Without
2 = With
Digit 22 - Filtration
A = G4 (50 mm) Filters
B = G4 (50 mm) + F7 (100 mm) lters
C = G4 (50 mm) + F9 (100 mm) lters
D = F5 (50 mm) + F7 (100 mm) lters
Digit 23 - Temperature Zone sensor
X = Without
A = Duct-Mounted Zone Sensor
B = Wall-Mounted Zone Sensor
Digit 24 - Room User Interface
X = Without
A = Wall-Mounted Interface THS04
B = Conventional Thermostat
C = Wall Mounted Interface PGD1
Digit 25 - CO
2
sensor
X = Without
1 = CO
2
Sensor Duct-Mounted
2 = CO
2
Sensor Wall-Mounted
Digit 26 - Factory assigned
X = Without
1 = With
Digit 27 - Airow Measurement
X = Without
A = Airow Measurement and Display
Digit 28 - Dirty lter detection
X = Without
1 = With
Digit 29 - Network protection relay
X = Phase Reversal Protection
A = PhaseReversal and Asymmetry Protection