RT-SVX060D-GB
6
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Unit Model Number Description
Digit 1 - Manufacturing location
E = Epinal France
Digit 2 - Unit model
I = Airnity
Digit 3 - Unit type
C = Cooling Only
H = Reversible Heat Pump
Digit 4-5-6 Unit size
140
150
170
190
220
250
270
Digit 7 - Efciency level
S = Standard efciency
Digit 8 - Refrigerant
A = R410A Factory Full Refrigerant Charge
8 = R410A Factory Refrigerant Pre-charge
2 = Nitrogen Charge (for units R410A)
B = R454B Factory Full Refrigerant Charge
3 = Nitrogen Charge (for units R454B)
Digit 9 - Unit voltage
E = 400 V - 3 Ph - 50 Hz
Digit 10 - Design Sequence
Digit 11 - Design Sequence
Digit 12 - Auxiliary Heat
X = Without
W = Hot Water Coil
E = Electric Heater
L = Modulating Gas Burner,126 kW
S = Modulating Gas Burner,160 kW
H = Modulating Gas Burner,194 kW
Digit 13 - Gas type
X = Without
1 = Propane Gas
2 = Natural Gas (G20)
3 = Natural Gas (G25)
Digit 14 - Airow conguration
D = Down Supply & Down Return
H = Horizontal Supply & Horizontal Return
I = Down Supply & Horizontal Return
J = Horizontal Supply & Down Return
Digit 15 - Available static pressure
1 = Standard External Static Pressure
2 = High External Static Pressure
Digit 16 - Operating map (cooling mode)
A = Standard Ambient
Digit 17 - Free cooling (Economizer)
X = Without (full recirculation)
A = Temperature Control
B = Enthalpy Control
Digit 18 - Heat Recovery Module
X = Without
R = Congured for Rotary Wheel
B = Congured for Rotary Wheel High Airow
Digit 19 - Dehumidication
X = Without
A = Dehumidication Control
Digit 20 - Outdoor coil treatment
B = Without
E = With
Digit 21 - Indoor coil treatment
1 = Without
2 = With
Digit 22 - Filtration
A = G4 (50 mm) Filters
B = G4 (50 mm) + F7 (100 mm) lters
C = G4 (50 mm) + F9 (100 mm) lters
D = F5 (50 mm) + F7 (100 mm) lters
Digit 23 - Temperature Zone sensor
X = Without
A = Duct-Mounted Zone Sensor
B = Wall-Mounted Zone Sensor
Digit 24 - Room User Interface
X = Without
A = Wall-Mounted Interface THS04
B = Conventional Thermostat
C = Wall Mounted Interface PGD1
Digit 25 - CO
2
sensor
X = Without
1 = CO
2
Sensor Duct-Mounted
2 = CO
2
Sensor Wall-Mounted
Digit 26 - Factory assigned
X = Without
1 = With
Digit 27 - Airow Measurement
X = Without
A = Airow Measurement and Display
Digit 28 - Dirty lter detection
X = Without
1 = With
Digit 29 - Network protection relay
X = Phase Reversal Protection
A = PhaseReversal and Asymmetry Protection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Airfinity XL IH190 and is the answer not in the manual?

Trane Airfinity XL IH190 Specifications

General IconGeneral
BrandTrane
ModelAirfinity XL IH190
CategoryChiller
LanguageEnglish

Related product manuals