16
CVHE-SVX02M-EN
Table 1. Clearance requirements (continued)
Evaporator Size
Shell Combo
A B C D E
in.
cm
in.
cm
in.
cm
in.
cm
in.
cm
Long/Long
53 134 187 474 419 1064 36 91 76 193
142 Medium/Long/
Extended
210 Long
Medium/Long
78 198 207 525 444 1127 44 111 92 233
Long/Long
58 147 187 474 424 1076 44 111 92 233
Extended/Long
58 147 209 530 469 1191 44 111 92 233
Long/Long
59 149 187 474 426 1082 47 119 102 259
250 Extended
Extended/Long
63 160 209 530 475 1206 43 109 115 292
NNoottee:: All dimensions are approximate; refer to the unit submittal package for exact dimensions for your unit.
General Weights
Weights (lb)
IImmppoorrttaanntt:: The weight information provided here
should be used for general information
only. Trane does not recommend using this
weight information for considerations
relative to chiller handling, rigging, or
placement. The large number of variances
between chiller selections drives variances
in chiller weights that are not recognized in
these tables. For specific weights for your
chiller, refer to your submittal package.
Table 2. Representative weights, 60 Hz chillers (lb)
Model
Comp Size
CPKW
Evap Size
Cond Size
Weights without Starters Weights with Starters
NTON EVSZ CDSZ
Operating Shipping Operating Shipping
CVHE
230–320
233
032S 032S
14828 13469
289 16508 15149
230–320 289 032S 032L 15433 13924 17113 15604
230–320 289 032L 032L 16277 14574 17957 16254
230–320 289 050S 050S 20035 17599 21715 19279
230–320 289 050S 050L 21001 18356 22681 20036
230–320 289 050L 050L 22352 19304 24032 20984
360–500 455 050S 050S 20717 18281 22397 19961
360–500 455 050S 050L 21683 19038 23363 20718
360–500 455 050L 050L 23034 19986 24714 21666
360–500 455 050S 080S 23200 20265 24880 21945
360–500 455 050L 080L 26793 22976 28473 24656
360–500 455 080S 080S 29854 25634 31534 27314
360–500 455 080S 080L 31442 26917 33122 28597
360–500 455 080L 080L 33463 28333 35143 30013
CVHF
350–570 588 050S 050S 20487 17984 22167 19664
350–570 588 050S 050L 21453 18741 23133 20421
350–570 588 050L 050L 22703 19567 24383 21247
350–570 588 050S 080S 22970 19968 24650 21648
350–570 588 050L 080L 26512 22557 28192 24237
350–570 588 080S 080S 31845 26997 32173 27715
UUnniitt CClleeaarraanncceess aanndd WWeeiigghhttss