Vent Line Sizing Reference
Table 12. “C” values used to determine rupture disk
vent line sizes; for use with the following
figure
Evap.
Size
(EVSZ)
Cond.
Size
(CDSZ)
“C” Values for Unit Components
Total
“C”
Value
Short
H.R.
Cond.
Long H.
R.
Cond.
Aux.
Cond.
Free
Cooling
Econ.
032S 032S 50.00
18.87 25.19 15.30 3.66032S 032L 61.32
032L 032L 65.09
050S 050S 64.20
23.55 31.45 15.30 5.50050S 050L 72.10
050L 050L 83.17
050S 080S 69.71
N/A N/A N/A N/A
050L 080L 90.52
080S 080S 86.48
29.06 38.80 15.30 5.38080S 080L 96.22
080L 080L 111.50
080L 142L 117.53
N/A N/A N/A N/A
142M 142L 127.49
51.01 56.80 15.30 7.13
142L 142L 134.89
142E 142L 143.11
210L 210L 149.91
Table 12. “C” values used to determine rupture disk
vent line sizes; for use with the following figure
(continued)
Evap.
Size
(EVSZ)
Cond.
Size
(CDSZ)
“C” Values for Unit Components
Total
“C”
Value
Short
H.R.
Cond.
Long H.
R.
Cond.
Aux.
Cond.
Free
Cooling
Econ.
250E 250L 175.74
N/A
62.12 15.30
N/A
210D 210D 112.93
N/A N/A
15.30 7.13
250D 250D 122.62
250M 250M 146.36
15.30
N/A
250X 250X 164.74
Notes:
1. Rupture disk diameter is 3 in. (76.2 mm), with the exception of
250E evaporator/250L condenser units with heat recovery which
have a rupture disk diameter of 4 in. (101.6 mm).
2. To determine the total “C” value for a specific unit, add the
appropriate “C” values for the evaporator, standard condenser, and
economizer. If the unit is equipped with any options (e.g., heat
recovery, free cooling, or an auxiliary condenser), add the
applicable “C” values to this total. With this new sum, refer to the
following figure to determine the vent-line pipe diameter.
3. If piping multiple rupture disks to a common vent line, first
determine the total “C” value for each rupture disk, then add all “C”
values together and apply the result to the following figure.
4. RuptureGuard™ size based on “C” value:
3-in. (76.2 mm) valve: “C” value 0 to 104.20
4-in. (101.6 mm) valve: C value 104.21 to 223.9
RuptureGuard™ is not available for 250E evaporator/250L
condenser units with heat recovery.
VVeenntt PPiippiinngg

Table of Contents

Other manuals for Trane CVHG

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CVHG and is the answer not in the manual?

Trane CVHG Specifications

General IconGeneral
BrandTrane
ModelCVHG
CategoryChiller
LanguageEnglish

Related product manuals