Table 18 HMP60 calculated parameters
Property Description/Value
Measurement ranges
Dew point temperature −40 … +60 °C (−40 … +140 °F)
Wet bulb temperature −40 … +60 °C (−40 … +140 °F)
Absolute humidity
0 … 130 g/m
3
(0 … 57 gr/ft
3
)
Mixing ratio 0 … 153 g/kg (0 … 1069 gr/lb)
Enthalpy −40 … 459 kJ/kg (−9.6 … 207 BTU/lb)
Table 19 HMP60 operating environment
Property Description/Value
Operating temperature −40 … +60 °C (−40 … +140 °F)
EMC compliance EN 61326-1, industrial environment
Table 20 HMP60 inputs and outputs
Property Description/Value
Power consumption 1 mA average, max. peak 5 mA
Operating voltage
1)
With 1 V / 2.5 V output 5 … 28 VDC
With 5 V output 8 … 28 VDC
With loop power converter 8 … 28 VDC
With digital output 5 … 28 VDC
Start-up time
Probes with analog output 4 s at operating voltage 13.5 … 16.5 VDC
2 s at other valid operating voltages
Probes with digital output 1 s
Outputs
2 channels 0 … 1 VDC / 0 … 2.5 VDC / 0 … 5 VDC / 1 … 5 VDC
1-channel loop-power converter (separate
module, compatible with humidity accuracy
only)
4 … 20 mA
Digital output (optional) RS-485 2-wire half duplex, supports Modbus
RTU
Chapter 9 – Technical data