Manual Manual 37223E 37223E easYgen-3000 easYgen-3000 Series Series (Package (Package P1) P1) - - Genset Genset ControlControl
© © Woodward Woodward Page Page 37/6737/67
Voltage Measuring: Busbar (System 1), Parameter Setting 'Voltage Measuring: Busbar (System 1), Parameter Setting '1Ph 2W
1Ph 2W' (1-phase, 2-wire)' (1-phase, 2-wire)
NOTE
NOTE
The 1-phase, 2-wire measurement may be performed phase-neutral or phase-phase. Please note The 1-phase, 2-wire measurement may be performed phase-neutral or phase-phase. Please note toto
configure and wire the easYgen consistently. Refer to the Configuration Manual 37224 configure and wire the easYgen consistently. Refer to the Configuration Manual 37224 for more infor-for more infor-
mation.mation.
''1Ph 2W
1Ph 2W' Phase-Neutral Measuring' Phase-Neutral Measuring
NN
L1L1
NN
A2A2A1A1
AA
A6A6A5A5
L1
L1
NN
NN
B5B5
B6B6
A1A1
A2A2
AA
Figure 6-27: Voltage measuring - busbar PT windings, 1Ph 2W (phase-neutral)Figure 6-27: Voltage measuring - busbar PT windings, 1Ph 2W (phase-neutral)
Busbar voltage 1Ph 2WBusbar voltage 1Ph 2W
[1[1]]
3377 3399
L1L1 NN
44003388
[[44]] [[11]] [[44]]
G
GCCBB
LL11
NN
LL11
NN
M
MCCBB
Figure 6-28: Voltage measuring - busbar measuring inputs, 1Ph 2W (phase-neutral)Figure 6-28: Voltage measuring - busbar measuring inputs, 1Ph 2W (phase-neutral)
1Ph 2W
1Ph 2W
Wiring Wiring terminals terminals NoteNote
Rated Rated voltage voltage (range) (range) [1] [1] 100 100 V V (50 (50 to to 130 130 VV
eff.eff.
) ) [4] [4] 400 400 V V (131 (131 to to 480 480 VV
eff.eff.
))
1111
Measuring Measuring range range (max.) (max.) [1] [1] 0 0 to to 150 150 Vac Vac [4] [4] 0 0 to to 600 600 VacVac
easYgen easYgen terminal terminal 37 37 39 39 --- --- --- --- 38 38 40 40 --- --- ------
Phase Phase L1 L1 N N --- --- --- L1 --- L1 N N --- --- ------
Table 6-17: Voltage measuring - terminal assignment Table 6-17: Voltage measuring - terminal assignment - busbar, 1Ph 2W (phase-neutral)- busbar, 1Ph 2W (phase-neutral)
1111
For different voltage syFor different voltage systems, different wiring terminals have to be used. Incorrect measurements are possible if both vostems, different wiring terminals have to be used. Incorrect measurements are possible if both voltage systems useltage systems use
the same N terminal.the same N terminal.