2
Reference Sections
A Environmental Limits
ACS140 Stationary Use
Storage and Transportation
in the Protective Package
Installation Site
Altitude
• 0...1000 m if P
N
and
I
2
100%
• 1000...2000 m if P
N
and I
2
derated 1%
every 100 m above
1000 m
-
Ambient
Temperature
• 0...40 °C (0...30 °C if
f
sw
=16 kHz)
• max. 50°C if P
N
and
I
2
derated to 80%
and f
sw
= 4 kHz
-40...+70 °C
Relative Humidity <95% (non condensing)
Contamination
Levels
(IEC 721-3-3)
No conductive dust allowed.
The ACS140 should be installed in clean and dry air,
free from dripping water, according to IP classification.
Cooling air must be clean, free from corrosive materials
and electrically conductive dust (pollution degree 2).
The installation room must be locked or tool-openable.
• chemical gases:
Class 3C2
• solid particles: Class
3S2
Storage
• chemical gases: Class
1C2
• solid particles: Class 1S3
Transportation
• chemical gases: Class
2C2
• solid particles: Class 2S2
www.barghmaher.org