39
ACS140 Complete Parameter List
Initially, only the so called basic parameters (shaded grey in Table 1) are
visible. The menu function -LG- is used to make the full parameter set visible.
S = Parameters can be modified only when the drive is stopped.
M = Default value depends on the selected macro (*).
Table 1 Full parameter set.
Code Name Range Resolution Default User S M
Group 99
START-UP DATA
9902
APPLIC MACRO 0-7 1 0 (FACTORY) !
9905
MOTOR NOM VOLT 200, 208,220,
230, 240,380,
400, 415,440,
460, 480 V
1 V 230/400 V !
9906
MOTOR NOM CURR 0.5*I
N
- 1.5*I
N
0.1 A I
N
!
9907
MOTOR NOM FREQ 0-300 Hz 1 Hz 50 Hz !
9908
MOTOR NOM SPEED 0-3600 rpm 1 rpm 1440 rpm !
Group 01
OPERATING DATA
0102
SPEED 0-9999 rpm 1 rpm -
0103
OUTPUT FREQ 0-300 Hz 0.1 Hz -
0104
CURRENT - 0.1 A -
0105
TORQUE -100 - 100 % 0.1 % -
0106
POWER - 0.1 kW -
0107
DC BUS VOLTAGE 0-679 V 0.1 V -
0109
OUTPUT VOLTAGE 0-480 V 0.1 V -
0110
ACS 140 TEMP 0-150 °C0.1 °C-
0111
EXT REF 1 0-300 Hz 0.1 Hz -
0112
EXT REF 2 0-100 % 0.1 % -
0113
CTRL LOCATION 0-2 1 -
0114
RUN TIME 0-99.99 kh 0.01 kh -
0115 kWh
COUNTER 0-9999 kWh 1 kWh -
0116
APPL BLK OUTPUT 0-100 % 0.1 % -
0117
DI1-DI4 STATUS 0000-1111
(0-15 decimal)
1-
0118
AI1 0-100 % 0.1 % -
0119 AI2 0-100 % 0.1 % -
0121
DI5 & RELAYS 0000-0111
(0-7 decimal)
1-
0122
AO 0-20 mA 0.1 mA -
0124
ACTUAL VALUE 1 0-100 % 0.1 % -
0125
ACTUAL VALUE 2 0-100 % 0.1 % -
0126
CONTROL DEV -100-100 % 0.1 % -
0127
ACTUAL VALUE -100-100 % 0.1 % -
0128
LAST FAULT 0-22 1 0
0129
PREVIOUS FAULT 0-22 1 0
0130
OLDEST FAULT 0-22 1 0