R Type Series and Technical Data
* Derate ambient temperature to 30 °C or derate P
N
and I
2
to 90 % (see I
2
(8 kHz)).
** Derate ambient temperature to 30 °C and derate P
N
and I
2
to 75 % (see I
2
(16 kHz)).
*** Fuse type: UL class CC or T. For non-UL installations IEC269 gG.
Use 60 °C wire for an ambient temperature of 45 °C or less and use 75 °C wire for
ambient temperature between 45 °C and 50 °C.
Standard 200 V series
Nominal motor P
N
kW 0.12 0.18 0.25 0.37 0.55
1~ Input ACS141- K18-1 K25-1 K37-1 K75-1 1K1-1
3~ Input ACS143- - - - K75-1 1K1-1
Frame size A
Nominal ratings
(See H) Unit
Input voltage U
1
V 200 V-240 V ±10 % 50/60 Hz
(ACS141: 1~, ACS143: 3~)
Continuous output current I
2
(4 kHz)
A 1.0 1.4 1.7 2.2 3.0
Continuous output current I
2
(8 kHz)
A 0.9 1.3 1.5 2.0 2.7
Continuous output current I
2
(16 kHz)
A 0.8 1.1 1.3 1.7 2.3
Max. output current I
2 max
(4 kHz)
A 1.5 2.1 2.6 3.3 4.5
Max. output current I
2 max
(8 kHz)
A 1.4 2.0 2.3 3.0 4.1
Max. output current I
2 max
(16 kHz)
A 1.1 1.5 1.9 2.4 3.3
Output voltage U
2
V0 - U
1
3~
Input current I
1
1~ A 2.7 4.4 5.4 6.9 9.0
Input current I
1
3~ A - - - 3.2 4.2
Switching frequency kHz 4 (Standard)
8 (Low noise *)
16 (Silent **)
Protection limits (See P)
Overcurrent (peak) A 3.2 4.5 5.5 7.1 9.7
Overvoltage:
Trip limit V DC 420 (corresponds to 295 V input)
Undervoltage:
Trip limit V DC 200 (corresponds to 142 V input)
Overtemperature
°C 90 (heat sink)
Max. wire sizes
Max. motor cable length m 50 50 50 75 75
Power terminals mm
2
4 single core / torque 0.8 Nm
Control terminals mm
2
0.5 - 1.5 (AWG22...AWG16) / torque
0.4 Nm
Line fuse 1~ ***, ACS141- A 6 6 10 10 10
Line fuse 3~ ***, ACS143- A - - - 6 6
Power losses
Power circuit W 7 10 12 13 19
Control circuit W 8 10 12 14 16
www.barghmaher.org