Application Macro Factory (0)
This macro is intended for applications where there is no control panel
available. It provides a general purpose 2-wire I/O configuration.
The value of parameter 9902 is 0. DI4 is not connected.
*Note! DI 4 is used to configure ACS140. It is read only once when power is
connected. All parameters marked with * are determined by the DI4 input.
Factory (0) parameter values:
Input signals Output signals DIP switch S1
• Start, stop and direction (DI1,2) • An. output AO: Frequency
• Analogue reference (AI1) • Relay output 1: Fault
• Constant speed 1 (DI3) • Relay output 2: Running
• Ramp pair 1/2 selection (DI5)
*1001
EXT 1 COMMANDS 2 (DI1,2) 1106 EXT REF2 SELECT 0 (KEYPAD)
1002
EXT 2 COMMANDS 0 (NOT SEL) *1201 CONST SPEED SEL 3 (DI3)
1003
DIRECTION 3 (REQUEST) 1601 RUN ENABLE 0 (NOT SEL)
1102
EXT1/EXT2 SEL 6 (EXT1) 2105 PREMAGN SEL 0 (NOT SEL)
1103
EXT REF1 SELECT 1 (AI1) 2201 ACC/DEC 1/2 SEL 5 (DI5)
S1:1:U
ON ON
Control
Terminal s
Function
1SCR
2 AI 1 External reference 1; 0...10 V <=> 0...50 Hz
3AGND
4 10 V Reference voltage 10 VDC
5 AI 2 Not used
6AGND
7 AO Output frequency 0...20 mA <=> 0...50 Hz
8AGND
9 +12 V +12 VDC
10 DCOM
11 DI 1 Start/Stop. Activate to start ACS140
12 DI 2 Fwd/Rev. Activate to reverse rotation direction
13 DI 3 Constant speed 1. Default: 5Hz
14 DI 4 Leave unconnected!*
15 DI 5 Ramp pair selection. Activate to select ramp pair 2.
Defaults: 5 s (ramp pair 1), 60 s (ramp pair 2)
16 RO 1A Relay output 1
Fault: open
17 RO 1B
18 RO 2A Relay output 2
Running: closed
19 RO 2B