HVC 450 kW E-Bus Charger Installation Guide
Revision: 1.2 COMPANY CONFIDENTIAL
Date released: 16-08-2018 Page 48 of 128
Use local regulations and datasheet of the manufacturer to determine the cable diameter for
the DC power cables. Recommended cable for the 450 kW system is 185 mm
2
(= 350 MCM)
(with a reinforced isolation > 5400 V DC) for a distance until 492.13 ft.
4.4.5. Cables between the Power Cabinets
The following cables are not in the scope of supply of ABB.
1x GND cable;
1x Interlock cable;
1x CAN cable.
For detailed information about type of glass fiber cable which are needed,
see Communication glass fiber cable on Page 21.
For the overview of the grounding of the system, see Appendix J Ground
overview of the system on Page 127.
4.4.6. Cable specification list
Tables below provides general specifications for the needed cables. Use these tables to
select cables, taking into account local installation conditions, cable length, cable
temperature rating, losses and local regulations.
AC and DC power cables
Min – Max external
diameter to fit through
gland
Tinned copper or
aluminum conductor, fine
wire
stranded acc. to VDE
0295 cl.5/IEC Cl.5
Fine strand copper wire
acc. to VDE 0295 Cl. 5/
IEC 60228 Cl. 5
Bare copper, fine wired,
bunch stranded acc. to
VDE 0295 Cl.5/IEC Cl.5
Special rubber or PVC
(outdoor use, UV-
protected, oil resistant)
Special PVC (outdoor
use, UV-protected, oil
resistant)
Special PVC (outdoor
use, UV-protected, oil
resistant)
600/1000 Vac
900/1500 Vdc
Ambient Temperature
range
-40ºC to 105ºC,
permissible conductor
operating
temperature +90°C
Color for US Acc. to US
National Electrical Code
and for Canada Acc. to
the CEC (Canadian
Electric Code)