Section-10
04-3004_S10_TDS_ABB_POWERSCALE_10-50 kVA_EN_150113.doc Page 7/20 ABB
Printed in Switzerland – Modifications reserved
10.4 BATTERY CHARACTERISTICS
Min/Max number of 12V
Battery Blocks per string
Min/Max number of 12V
NiCd-Cells
Maximum Battery
Charger Current
Ripple free ; IU (DIN 41773)
Temperature compensation
ready
Standard (temp. sensor optional)
Automatic and periodically (adjustable)
Maintenance free VRLA or NiCd
Note : (*) Depending of the effective load in kW used by system (see table below and table in chapter 10.10.1).
Max no. for internal batteries is 48, max no. for extern batteries is 50
Description
Cabinet Type
Maximum Power in [kW]
6 8 9 6 8 9 8 10 12 13.5 8 10 12 13.5 9 12 16 18 9 12 16 18 12 16 20 22.5
Minimum number of
battery blocks per String
20 24 26 20 24 26 24 28 32 36 24 28 32 36 26 32 40 44 26 32 40 44 32 40 46 48
Maximum number of
battery blocks intern the
PSC cabinet
Description
Cabinet Type
Maximum Power in [kW]
12 16 20 22.5 16 20 24 27 18 25 32 36 30 35 40 45
Minimum number of
battery blocks per String
24 32 40 46 16 20 24 28 18 26 32 36 30 34 40 46
Maximum number of
internal battery blocks 7/9
Ah
3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48 3x48
Maximum number of
internal battery blocks 28
Ah
1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48 1x48