EasyManuals Logo
Home>ABB>Control Unit>rec670

ABB rec670 User Manual

ABB rec670
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
8.2.3 View event recordings
The Event recording section in the Disturbance report shows the recording number.
The path in the HMI is shown below.
Main menu/Disturbance records/Record xx/Event recording
8.2.4
View trip values
In the Trip values section of a disturbance recording both the pre-fault and the fault
values for current, voltage and phase angle can be viewed. The recording number
and Trig time are also displayed. The path in the HMI is shown below.
Main menu/Disturbance records/Record xx/Trip Values
8.2.5 Recalculate distance to fault
This screen displays the fault loop with reactance and resistance values. To
recalculate the distance to fault, press the E key on the keypad.
In the Recalculate distance to fault section in a disturbance record it is possible not
only to view fault data but to recalculate the distance to a fault. By taking into
account peripheral influences like the resistance and reactance of other lines in the
immediate network area new distances can be calculated. The reactance and
resistance in the forward direction have the suffix B and in the reverse direction
they have the suffix A.
Recalculation may be necessary in cases where the data from a different fault loop
needs to be calculated. In three phase faults only one loop is shown in the
disturbance record. When recalculating, a different fault loop can be selected. The
path in the HMI is shown below.
Main menu/Disturbance records/Record xx/Recalc distance to fault
8.3 Trigger a disturbance report manually
Using the manual trigger generates an instant disturbance report. Use this function
to get a snapshot of the monitored line. Follow the path below and answer yes in
the Execute manual trig dialog box.
Main menu/Disturbance records/Manual trig
Section 8 1MRK 511 188-UEN C
Handle disturbances
38
Operator's manual

Table of Contents

Other manuals for ABB rec670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB rec670 and is the answer not in the manual?

ABB rec670 Specifications

General IconGeneral
BrandABB
Modelrec670
CategoryControl Unit
LanguageEnglish

Related product manuals