11.6.11.3 Tripping logic SMPPTRC
Main menu/Test/Function status/Logic/TripLogic(PTRC94)/
TRP
Displays available instances of the function SMPPTRC with some measurements
per instance. The output data from each measurement is boolean and indicates the
existence of various trip signals. For example, if the output from parameter TRL1
is one, this indicates that a trip signal from phase L1 has been generated.
11.6.11.4 Trip matrix logic TMAGGIO
Main menu/Test/Function status/Logic/TripMatrix(GGIO)/TR
Displays available instances of the function TMAGGIO with some boolean output
values per instance. The output signals from this function block are typically
connected to other logic blocks or directly to IED output contacts.
11.6.11.5 Logic gate
Main menu/Test/Function status/Logic/LogicGate/GT
Displays available instances of the gate output. The output data type is an integer
with a possible value from 0 to 255.
11.6.11.6 Logic SR/RS memory
Main memory/Test/Function status/Logic/LogicSRMemory/SM
Displays available instances of the function SM. The output data presented in the
HMI is boolean and indicates whether or not a signal is present. For example, an
output of one from SM01 OUT indicates that a signal exists on that output.
11.6.11.7 Logic SR/RS Memory qt
Main memory/Test/Function status/Logic/LogicSRMemory_qt/SN
Main memory/Test/Function status/Logic/LogicRSMemory_qt/SN
Displays available instances of the function SM. The output data presented in the
HMI is boolean and indicates whether or not a signal is present. For example, an
output of one from SM01 OUT indicates that a signal exists on that output.
11.6.11.8 Logic timer set
Main menu/Test/Function status/Logic/LogicTimerSet/TS
Displays available instances of the function (TS). The output data type is boolean
and indicates whether the output from the timer pickup is delayed (ON) or if the
drop out (OFF) is delayed.
1MRK 511 188-UEN C Section 11
Test the IED
85
Operator's manual

Table of Contents

Other manuals for ABB rec670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB rec670 and is the answer not in the manual?

ABB rec670 Specifications

General IconGeneral
BrandABB
Modelrec670
CategoryControl Unit
LanguageEnglish

Related product manuals