Horizontal communication via GOOSE for interlocking IntlReceive
Main menu/Test/Function status/Communication/Station communication/
ReceivingInterlInfo/GR
The Receiving Interlock information available here indicates the state of various
apparatus such as whether they are in a closed or open position and if their status is
valid. Several apparatuses can be displayed. There are also indications of
reservation
requests, reservation granted and the validity of data and communication.
11.6.13 Setting groups
Main menu/Test/Function status/Setting groups
Displays available setting groups and indicates which of them is in use.
11.6.14 Test
Main menu/Test/Function status/Test
Displays the parameters ACTIVE, OUTPUT and SETTING. The ACTIVE
parameter indicates whether the IED is in test mode or not, the OUPUT parameter
indicates whether test mode has been activated by a binary input and the SETTING
parameter indicates whether or not test mode has been activated by a setting. The
output data is binary (0 or 1).
11.6.15 Authorization
Main menu/Test/Function status/Authorization
Shows if any user is logged on and if any user is blocked by invalid password.
11.7 LED Test
Main menu/Test/LED test
The Test LEDs menu enables the operator to activate LEDs manually. LEDs that
do not light up are defective. Defective LEDs are also logged in Disturbance
records under Monitoring.
11.8 Line differential test
Main menu/Test/Line differential test/LineDiffLogic
1MRK 511 188-UEN C Section 11
Test the IED
87
Operator's manual

Table of Contents