Table 33: Test points for phase-to-earth L3-E (Ohm/Loop)
Test point Reach Value Comments
1 X (2 x X1
set
+X0
set
)/3
R 0
2 X (2 x X1
set
+ X0
set
)/3
R 2 x R1
set
+ R0
set
)/3
3 X 0.8 x (2 x X1
set
+ X0
set
)/3
R 0.8 x (2 x R1
set
+ R0
set
)/3
+RFPEZx
set
4 X 0.5 x (2 x X1
set
+ R0
set
)/3
R 0.5 x (2 x R1
set
+R0
set
)/3 +
RFPEZx
set
5
X 0.85 x RFPEZx
set
x tan(ArgLd
set
) ArgLd = angle for the maximal load
transfer
R 0.85 x RFPEZx
6 X RLdFw
set
x tan(ArgLd
Set
)
R RLdFw
set
7 X 0
R RLdFw
set
8 X –02143 x RLdFw
set
Exact: 0.8 x RFPEZx x tan
(ArgDir=20°)
R 0.8 x RLdFw
set
9 X –0.8 x RLdFw
set
x tan(ArgDir=20°)
R 0.8 x RLdFw
set
10 X 0.17 x (2 x X1
set
+ X0
set
) Exact: 0.5 x (2 x X1
set
X0
set
)/3
R
-0.36 x (2 x X1
set
+ X0
set
) Exact: 0.5 x (2X1
set
+ X0
set
)/(3 x
tan(AgNegDir=30°)
11 X 0.27 x (2 x X1
set
+X0
set
) Exact: 0.8 x (2 x X1
set
+ X0
set
)/3
R
–0.57 x (2 x X1
set
+ X0
set
) Exact: 0.8 x (2X1
set
+ X0
set
)/(3 x
tan(AgNegDir=30°)
12 X 0.5 x (2 x X1
set
+ X0
set
)/3
R 0.5 x (2 x R1
set
+ R0
set
)/3
13 X 0
R RFPEZx
11.4.8.1 Measuring the operating limit of set values
GUID-24FEBCE7-3409-4204-AA15-A1E0A1605866 v3
Procedure:
1. Subject the
IED to healthy normal load conditions for at least two seconds.
2. Apply the fault condition and slowly decrease the measured impedance to
find the operating value of the phase-to-phase fault for zone 1 according to
1MRK 505 378-UEN A Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC 139
Commissioning manual