EasyManua.ls Logo

ABB RED670 User Manual

ABB RED670
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #264 background imageLoading...
Page #264 background image
11.12.1.3 1ph/2ph/3ph operating mode
SEMOD54375-143 v5
In addition to other tests, the following tests, which depend on the complete
configuration of an IED, should be carried out.
Procedure
1. Make sure that AutoLock
and TripLockout are both set to Off.
2. Initiate different single-phase-to-earth faults one at a time.
Take an adequate time interval between faults into consideration, to overcome
a reclaim time, which is activated by the autorecloser function SMBRREC.
Only a single-phase trip should occur for each separate fault and only one of
the trip outputs (TRLn) should be activated at a time. Functional outputs
TRIP and TR1P should be active at each fault. No other outputs should be
active.
3. Initiate different phase-to-phase faults one at a time.
Take an adequate time interval between faults into consideration, to overcome
a reclaim time which is activated by SMBRREC. Only a two-phase trip
should occur for each separate fault and only corresponding two trip outputs
(TRLn) should be activated at a time. Functional outputs TRIP and TR2P
should be active at each fault. No other outputs should be active.
4. Initiate a three-phase fault.
Take an adequate time interval between faults into consideration, to overcome
a reclaim time, which may be activated by SMBRREC. Only a three-phase
trip should occur for the fault and all trip outputs (TRLn) should be activated
at the same time. Functional outputs TRIP and TR3P should be active at each
fault. No other outputs should be active.
5. Initiate a single phase-to-earth fault and switch it off immediately when the
trip signal is issued for the corresponding phase. Initiate the same fault once
again within the reclaim time of the used SMBRREC.
A single-phase fault shall be given at the first fault. A three-phase trip must
be initiated for the second fault. Check that the corresponding trip signals
appear after both faults. Functional outputs TRIP, TRLn and TR1P should be
active during first fault. No other outputs should be active. Functional outputs
TRIP, all TRLn and TR3P should be active during second fault.
6. Initiate a single phase-to-earth fault and switch it off immediately when the
trip signal is generated for the corresponding phase. Initiate the second single-
phase-to-earth fault in one of the remaining phases within the time interval,
shorter than tEvolvingFault (default setting 2.0s) and shorter than the dead-
time of SMBRREC, when included in the protection scheme.
Check that the second trip is a three-phase trip and that a three-phase
autoreclosing attempt is given after the three-phase dead time. Functional
outputs TRIP, TRLn and TR1P should be active during first fault. No other
outputs should be active. Functional outputs TRIP, all TRLn and TR3P should
be active during second fault.
7. Initiate a phase-to-phase fault and switch it off immediately when the trip
signal is issued for the corresponding two phases. Initiate a second phase-to-
Section 11 1MRK 505 378-UEN A
Testing functionality by secondary injection
258 Line differential protection RED670 2.2 IEC
Commissioning manual

Table of Contents

Other manuals for ABB RED670

Question and Answer IconNeed help?

Do you have a question about the ABB RED670 and is the answer not in the manual?

ABB RED670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Product TypeProtection Relay
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, IEC 60870-5-103, DNP3
Operating Temperature Range-25°C to +55°C
Protection FunctionsDifferential protection, distance protection, overcurrent protection
OutputsBinary outputs
EnclosureIP54
Mounting19" rack mounting

Summary

Introduction to Commissioning Manual

This Manual

Provides instructions on commissioning the IED, testing external circuitry, parameter setting, and verification by secondary injection.

Safety Information

Symbols on the Product

Describes safety symbols like general warnings, laser product warnings, and hot surface warnings.

Warnings

Provides crucial warnings regarding electrical safety, personnel qualifications, and hazardous voltages during operation.

Starting Up the IED

Checking the Power Supply

Details precautions for connecting the power supply and checking voltage range and polarity.

Setting Up Communication between PCM600 and the IED

Explains how to establish communication using Ethernet and TCP/IP, including setting up IP addresses.

Checking CT Circuits

Provides guidelines for checking current transformer circuits, including wiring, polarity, resistance, and excitation tests.

Checking VT Circuits

Details checks for voltage transformer circuits, including wiring, polarity, earthing, phase relationship, and insulation resistance.

Configuring the IED and Changing Settings

Configuring Analog CT Inputs

Details the configuration of analog input channels, especially CT settings, for accurate measurement and protection.

Establishing Connection and Verifying the IEEE C37.118/1344 Communication

Setting the TCP/UDP Client Communication

Provides steps to set PMU Connection Tester parameters for establishing IEEE C37.118 connection.

Testing IED Operation

Preparing for Test

Lists IED test requirements, including settings, configuration diagrams, and necessary test equipment.

Activating the Test Mode

Describes how to put the IED into test mode to block protection functions and enable testing.

Verifying Analog Primary and Secondary Measurement

Guides on verifying analog input values by injecting current and voltage, and checking service values on HMI.

Testing the Protection Functionality

Explains that each protection function must be tested individually by secondary injection, verifying levels, timers, and signals.

Forcing of Binary Input/Output Signals for Testing

Describes the concept and methods (LHMI, PCM600, TESTMODE block) for forcing binary signals.

Testing Functionality by Secondary Injection

Differential Protection

Details testing procedures for various differential protection functions, including high impedance and line differential.

Impedance Protection

Covers testing procedures for impedance protection functions like distance protection zones and phase selection.

Current Protection

Provides detailed steps for testing various current protection functions, including overcurrent and earth fault protection.

Checking the Directionality

Testing the Directionality of the Distance Protection

Guides on testing directionality of distance protection using information from ZMFPDIS, ZMFCPDIS, ZDRDIR, or ZDMRDIR functions.

Commissioning and Maintenance of the Fault Clearing System

Commissioning Tests

Covers verification of protection functions, circuit checks, and final directional function verification.

Trip Circuit Check

Emphasizes checking the trip circuit health for correct protection operation, especially if trip-circuit supervision is absent.

Troubleshooting

Checking the Self Supervision Signals

Guides on navigating menus to find the cause of internal failures indicated by the HMI flashing green LED.

Fault Tracing

Explains how to interpret internal fault indications on the HMI and retrieve detailed information from the SMS part.

Repair Instruction

Provides safety warnings and procedures for disassembling and reassembling the IED, including handling ESD-sensitive components.

Related product manuals