EasyManua.ls Logo

ABB RED670 User Manual

ABB RED670
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #285 background imageLoading...
Page #285 background image
Test instructions for protection IEDs to be tested
T
est records from previous commissioning and maintenance tests
List of valid settings
Blank test records to fill in measured values
13.2.2.2 Recording
SEMOD56528-14 v2
It is of utmost importance to carefully record the test results. Special test sheets
covering the frequency of test, date of test and achieved test values should be used.
IED setting list and protocols from previous tests should be available and all results
should be compared for differences. At component failures, spare equipment is
used and set to the requested value. A note of the exchange is made and the new
measured values are recorded. Test records for several years of testing should be
stored in a common file for a station, or a part of a station, to give a simple
overview of the period of testing and achieved test values. These test records are
valuable when analysis of service disturbances shall be done.
13.2.2.3 Secondary injection
SEMOD56528-17 v2
The periodic maintenance test is done by secondary injection from a portable test
set. Each protection shall be tested according to the secondary injection test
information for the specific protection IED. Only the setting values adopted shall
be checked for each protection function. If the discrepancy between obtained value
and requested set value is too big the setting should be adjusted, the new value
recorded and a note should be made in the test record.
13.2.2.4 Alarm test
SEMOD56528-20 v4
When inserting the test handle the alarm and event signalling is normally blocked.
This is done in the IED by setting the event reporting to Off during the test. This
can be done when the test handle is inserted or the IED is set to test mode from the
local HMI. At the end of the secondary injection test it should be checked that the
event and alarm signalling is correct by activating the events and performing some
selected tests.
13.2.2.5 Self supervision check
SEMOD56528-23 v5
Once secondary testing has been completed, it should be checked that no self-
supervision signals are activated continuously or sporadically. Especially check the
time synchronization system, GPS or other, and communication signals, both
station communication and remote communication.
13.2.2.6 Trip circuit check
SEMOD56528-26 v5
When the protection IED undergoes an operational check, a tripping pulse is
normally obtained on one or more of the output contacts and preferably on the test
switch. The healthy circuit is of utmost importance for the protection operation. If
1MRK 505 378-UEN A Section 13
Commissioning and maintenance of the fault clearing system
Line differential protection RED670 2.2 IEC 279
Commissioning manual

Table of Contents

Other manuals for ABB RED670

Question and Answer IconNeed help?

Do you have a question about the ABB RED670 and is the answer not in the manual?

ABB RED670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Product TypeProtection Relay
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, IEC 60870-5-103, DNP3
Operating Temperature Range-25°C to +55°C
Protection FunctionsDifferential protection, distance protection, overcurrent protection
OutputsBinary outputs
EnclosureIP54
Mounting19" rack mounting

Summary

Introduction to Commissioning Manual

This Manual

Provides instructions on commissioning the IED, testing external circuitry, parameter setting, and verification by secondary injection.

Safety Information

Symbols on the Product

Describes safety symbols like general warnings, laser product warnings, and hot surface warnings.

Warnings

Provides crucial warnings regarding electrical safety, personnel qualifications, and hazardous voltages during operation.

Starting Up the IED

Checking the Power Supply

Details precautions for connecting the power supply and checking voltage range and polarity.

Setting Up Communication between PCM600 and the IED

Explains how to establish communication using Ethernet and TCP/IP, including setting up IP addresses.

Checking CT Circuits

Provides guidelines for checking current transformer circuits, including wiring, polarity, resistance, and excitation tests.

Checking VT Circuits

Details checks for voltage transformer circuits, including wiring, polarity, earthing, phase relationship, and insulation resistance.

Configuring the IED and Changing Settings

Configuring Analog CT Inputs

Details the configuration of analog input channels, especially CT settings, for accurate measurement and protection.

Establishing Connection and Verifying the IEEE C37.118/1344 Communication

Setting the TCP/UDP Client Communication

Provides steps to set PMU Connection Tester parameters for establishing IEEE C37.118 connection.

Testing IED Operation

Preparing for Test

Lists IED test requirements, including settings, configuration diagrams, and necessary test equipment.

Activating the Test Mode

Describes how to put the IED into test mode to block protection functions and enable testing.

Verifying Analog Primary and Secondary Measurement

Guides on verifying analog input values by injecting current and voltage, and checking service values on HMI.

Testing the Protection Functionality

Explains that each protection function must be tested individually by secondary injection, verifying levels, timers, and signals.

Forcing of Binary Input/Output Signals for Testing

Describes the concept and methods (LHMI, PCM600, TESTMODE block) for forcing binary signals.

Testing Functionality by Secondary Injection

Differential Protection

Details testing procedures for various differential protection functions, including high impedance and line differential.

Impedance Protection

Covers testing procedures for impedance protection functions like distance protection zones and phase selection.

Current Protection

Provides detailed steps for testing various current protection functions, including overcurrent and earth fault protection.

Checking the Directionality

Testing the Directionality of the Distance Protection

Guides on testing directionality of distance protection using information from ZMFPDIS, ZMFCPDIS, ZDRDIR, or ZDMRDIR functions.

Commissioning and Maintenance of the Fault Clearing System

Commissioning Tests

Covers verification of protection functions, circuit checks, and final directional function verification.

Trip Circuit Check

Emphasizes checking the trip circuit health for correct protection operation, especially if trip-circuit supervision is absent.

Troubleshooting

Checking the Self Supervision Signals

Guides on navigating menus to find the cause of internal failures indicated by the HMI flashing green LED.

Fault Tracing

Explains how to interpret internal fault indications on the HMI and retrieve detailed information from the SMS part.

Repair Instruction

Provides safety warnings and procedures for disassembling and reassembling the IED, including handling ESD-sensitive components.

Related product manuals