8.7 ABB Product Data Registration
The ABB Product Data Registration feature traces composition changes related to
the IED's SW or HW.
After a composition change, an LCT indication is seen on the LHMI at the IED start-
up. At this point, PCM600 should be connected to the IED as it reads the changed
data from the IED. The LCT indication is cleared in the same way as other indications.
If PCM600 is not connected to the IED, the indication is seen again after the IED's
reboot.
A071266 V2 EN
Figure 76: LCT indication
The number of composition changes can be seen from the Composition changes
parameter in Main Menu/Monitoring/IED status.
Section 8 1MRS756708 A
Commissioning
112 615 series