67N
Three phase CT
summated
Single CT
YN/D or YN/Y
transformer
Single phase-
to- ground fault
ANSI05000493_3_en.vsd
0
3I
alt
ANSI05000493 V3 EN-US
Figure 274: Step 1 fault calculation 1
The fault is located at the borderline between instantaneous and delayed operation of
the line protection, such as Distance protection or line residual overcurrent protection.
This calculation gives the current fed to the protection: 3I
0fault2
The setting of step 1 can be chosen within the interval shown in equation
433.
0fault 2 step1 0fault1
3I lowmar I 3I highmar× < < ×
EQUATION1455 V2 EN-US (Equation 433)
Where:
lowmar is a margin to assure selectivity (typical 1.2) and
highmar is a margin to assure fast fault clearance of busbar fault (typical 1.2).
Setting of step 2
SEMOD55591-57 v5
The setting of the sensitive step 2 is dependent of the chosen time delay
. Often a
relatively long definite time delay or inverse time delay is chosen. The current setting
Section 9 1MRK 504 163-UUS A
Current protection
548 Transformer protection RET670 2.2 ANSI
Application manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RELION RET670 and is the answer not in the manual?

ABB RELION RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Communication ProtocolsIEC 61850, IEC 60870-5-103, DNP3
Operating Temperature Range-25°C to +55°C
MountingRack Mounting
Input Voltage100-240 V AC
Protection FunctionsOvercurrent Protection
EnclosureIP20

Related product manuals