76 | RMC-100| 2105552MNAE
Programmable SCF or MCF or MMCF
Programmable SCF or MCF or MMCF
Programmable SCFM or MCF or MMCF
Last volume calculation period
The RMC has a factory default display group. Create and define additional groups as necessary.
Program the display groups and display items per Table 5-1.
By default, each display item remains on the display for five seconds. Change the display duration to
any value from 1 to 255 seconds, or zero (0) so the item does not display. Also change the
engineering units and data format for the display, if necessary.
The annunciators are programmable. Assign the annunciator to an application to display specific
alarms on the LCD (Table 5-2
).
Table 5-2: Annunciator indicators
LCD)
No annunciators display. There is no power to the RMC.
Low lithium battery alarm. When LL (low lithium) displays, the lithium battery
voltage is below 2.5 Vdc. A new lithium battery measures approximately 3.6 Vdc.
Low Charger displays if the RMC battery charging voltage is (+) 0.4 Vdc, or is less
than or equal to battery voltage
Exception Alarm Processing
The number that represents the Display Group.
The value above the Data High Limit value on the Display Item Setup screen.
The value below the Data Low Limit value specified on the Display Item Setup
screen.
Transmitting Data: sending a response
Receiving Data: processing a response
Nak: Negative acknowledgement with packet list
Positive acknowledge of receipt of request
Waiting for Acknowledgement: waiting for response after transmission
ID Recognized. The ID is recognized but is awaiting sync.
Listen Cycle flashes when the remote port is active and running Totalflow Remote
Protocol. Flashes are in sync with the listening cycle that occurs at 1, 2 or 4 second
LevelMaster Protocol: LevelMaster protocol is the port assigned to this annunciator.
This displays when the device is connected to an MMI port.
This displays when the device is connected to a USB port.
The Totalflow Packet Protocol selected on this port.
The MODBUS® ASCII protocol for the port assigned to this annunciator.
The Valve Control option is on Expanded I/O board (plug-in RTU). Other valve
control symbols do not apply.
The request was received.
The valve control option is installed. Process value (Process value, PV) is within the
user-assigned dead band.
The valve is in full open position.
The valve is in full closed position.