Publication 1747-UM011G-EN-P - June 2008
58 System Installation Recommendations
Typical Installation
The figure below consists of some components that make up a typical
installation.
Spacing Your Controller
The figure on the following page depicts acceptable layouts. Follow the
recommended minimum spacing to allow for convection cooling within the
enclosure. Air temperature in the enclosure must be kept within a range of
0 °C...60 °C (32 °F...140 °F).
1. NEMA-rated enclosure suitable for
your application and environment that
shields your controller from electrical
noise and airborne contaminants.
2. Disconnect device, to remove power
from the system
3. Fused isolation transformer or a
constant voltage transformer, as your
application requires
4. Master control relay/emergency-stop
circuit
5. Terminal blocks or wiring ducts
6. Suppression devices for limiting EMI
(electromagnetic interference)
generation
Disconnect
Device
Isolation
Transformer
SLC 500
Controller
MCR
(1)
(2)
(3)
(4)
(6)
(5)
ATTENTION
Vertical mounting is not recommended due to thermal
considerations.
IMPORTANT
Be careful of metal chips when drilling mounting holes for the
controllers. Do not drill holes above a mounted SLC 500
controller.

Table of Contents

Other manuals for Allen-Bradley SLC 500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SLC 500 and is the answer not in the manual?

Allen-Bradley SLC 500 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSLC 500
CategoryController
LanguageEnglish

Related product manuals