45
ENG
“EVD evolution” +030222041 - rel. 1.0 - 01.06.2008
Fig. 12.f
Note: the program On-line help can be accessed by pressing F1.
Copying the setup 12.3
On the Confi gure device page, once the new project has been created, to
transfer the list of confi guration parameters to another driver:
read the list of parameters from the source driver with the “Read” •
command;
remove the connector from the service serial port;•
connect the connector to the service port on the destination driver;•
write the list of parameters to the destination driver with the “Write” •
command.
Important: the parameters can only be copied between controllers
with the same code. Diff erent fi rmware versions may cause compatibility
problems.
Setting the default parameters12.4
When the program opens:
select the model from the range and load the associated list of •
parameters;
go to “Confi gure device”: the list of parameters will be shown, with the •
default settings.
connect the connector to the service serial port on the destination •
driver;
during the write procedure, the LEDs on the converter will fl ash. •
The driver parameters driver will now have the default settings.
Updating the driver and display 12.5
rmware
The driver and display fi rmware must be updated using the VPM program
on a computer and the USB/tLAN converter, which is connected to
the device being programmed (see paragraph 2.5 for the connection
diagram). The fi rmware can be downloaded from http://ksa.carel.com.
See the VPM On-line help.