WEIGHT DISTRIBUTION
POSITIONING
The units have been designed for outdoor installation in a fixed position.
Check that the fastening/support points are in level and can bear the weight of the unit (see weights and weight distribution).
Avoid installation in areas that may be subject to flooding.
Installations below ground level or near very high walls must be carefully assessed.
Place a layer of rubber between the base of the unit and the support to prevent noise and vibrations. Depending on the place of
installation (balconies or roofs), the unit should be placed on special antivibration mounts (in this case, flexible joints are required for
the water/aeraulic connections - joints are not supplied by Clivet).
Fasten the unit to the ground.
The choice of the location of the unit is of fundamental importance for correct operation. Obstacles that block the flow of air, difficulty
in air circulation, leaves or other objects that may block the exchanger coils, winds that contrast or excessively assist the air flow,
phenomena of stratification or air re-circulation and nearby sources of heat, can cause operating anomalies (increases in condensing
pressure, and consequently decreases in performance) or the shut-down the machine (due to high pressure).
Reception/Positioning
W3
W1 W2
W4
MN
O
W3
W1 W2
W4
P
W3
W1 W2
W4
"G"
5
9
175299085
5
9
9
7
7
SIZES 302 323 404 464 524 564 614
W1 kg 346 352 355 380 383 386 389
W2 kg 369 399 418 447 454 467 477
W3 kg 313 346 364 395 401 413 423
W4 kg 333 392 428 463 476 499 519
Operating weight kg 1361 1489 1565 1685 1714 1765 1808
Shipping weight kg 1347 1473 1548 1666 1695 1746 1789
SIZES 302 323 404 464 524 564 614
W1 kg 348 354 357 382 384 388 391
W2 kg 375 405 424 453 460 473 483
W3 kg 322 355 373 403 410 422 432
W4 kg 348 407 443 478 491 514 534
Operating weight kg 1393 1521 1597 1716 1745 1797 1840
Shipping weight kg 1378 1504 1579 1697 1726 1777 1820