33
®
Control
SETTING THE MAINTENANCE SET POINT
A maintenance SET POINT can be enabled for both COOLING and HEATING mode. This function, unless requested when ordering,
must first be enabled by an authorised CLIVET service centre. If the function is enabled, the sequence shown illustrates the phases to
be followed for entering the desired set point values. In addition, the maximum number of compressors enabled to operate during the
maintenance phase can also be set.
Purpose of the function: the unit, when switched OFF, remains active but in standby status. At preset intervals, the water pump is
activated (for a set time), so as to allow the temperature of chilled fluid to be measured. If the temperature is considered potentially
near the unit’s operating limits, the unit starts again so as to move the value ways from such limits.
1. Configuration menu
2. Parameter setting menu
3. H2O SYSTEM board menu
4. Cooling maintenance set point
5. Heating maintenance set point