InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 102
IL-NT-AMF-2.2-Reference Guide.pdf
TEST mode
The setpoint ReturnFromTEST influences the behavior of TEST mode.
Caution: The gen-set starts automatically and is always running in TEST mode!
The setpoint ReturnFromTEST = MANUAL
While TEST mode is selected, gen-set starts and is running unloaded.
To load the gen-set
a) Power cut comes or
b) MCB ON/OFF is pressed
When power cut: MCB is opened, after Transfer Del elapses, GCB is closed.
When the mains recovers gen-set stays supplying island load. To transfer the load back to the healthy
mains, press MCB ON/OFF button while controller is in AUT Mode. If genset will fail (shutdown or
other reason) and mains is healthy controller will transfer the load automatically back to mains.
Hint:
The controller does not respond to GCB ON/OFF , STOP, START
The load is automatically transferred back to the mains when any gen-set shut down protection
activates.
Test on load
When binary input Rem TEST OnLd is closed, the controller automatically transfers load from the
mains to the gen-set. Setpoint AMF Settings: ReturnFromTEST must be set to MANUAL, otherwise
controller will not transfer the load to gen-set. If the setpoint ReturnFromTEST is set to AUTO,
controller behaves like in common TEST mode (e.g. gen-set remains running but will not automatically
transfer the load, it will wait for mains fail).
The setpoint ReturnFromTEST = AUTO
While TEST mode is selected, gen-set is running unloaded.
When power cut comes the controller opens MCB.
After Return break elapses, GCB is closed.
When the mains recovers:
a) After MainsReturn Del the controller opens the GCB
b) After Transfer Del delay MCB is closed.
c) The engine stays running
To stop the gen-set select other mode than TEST
Hint:
The controller does not respond to GCB ON/OFF , MCB ON/OFF , STOP, START
Circuit breakers timing
Relation between Mains fail and MCB and start of gen-set
MCB Opens On = MAINSFAIL:
Mains fail is detected as Mains <V, Mains >V, Mains V Unbal, Mains <Freq, Mains >Freq. After
detection MCB is opened.
Hint:
When MCB feedback drop-out and measured mains electrical limits (voltage, frequency) are still in
limits, the controller switches MCB ON again.