InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 144
IL-NT-AMF-2.2-Reference Guide.pdf
PWM frequency 250Hz
Maximum current 0.5 A
Maximum switching voltage 36 VDC
Output resistance 1
Resolution 10 bits
IC-NT CT-BIO7 interface (optional card)
7 dedicated pins of the plug-in card’s terminal can be configured as binary inputs or outputs.
CURRENT MEASURING INPUT Number of inputs 1
Nominal input current (from CT) 5A
Load (CT output impedance) < 0.1
Max measured current from CT 10A
Current measurement tolerance 2% from Nominal current
Max peak current from CT 150A / 1s
Max continuous current 10A
(All values in RMS)
BINARY INPUTS Number of inputs 7
Input resistance 4.7k
Input range 0-36 VDC
Voltage level for close contact indication (Logical 1) <0.8 VDC
Voltage level for open contact indication (Logical 0) >2 VDC
Max voltage level for open contact indication 8-36 VDC
BINARY OPEN COLLECTOR OUTPUTS
Number of outputs 7
Maximum current per pin 0.5 A
Maximum switching common current 2A
Maximum switching voltage 36 VDC
Hint:
Binary inputs are not galvanically isolated.
IL-NT BIO8 interface (optional card)
Plugs into IL-NT controller EXTENSION MODULE port.
8 dedicated pins of the plug-in card’s terminal can be configured as binary inputs or outputs.
Binary inputs
Number of inputs 8
Input resistance 4,7kΩ
Input range 0-36 VDC
Voltage level for close contact indication (Logical 1) <0,8 VDC
Voltage level for open contact indication (Logical 0) >2 VDC
Max voltage level for open contact indication 8-36 VDC
Binary open collector outputs
Number of outputs 8
Maximum current per pin 0,5 A
Maximum switching common current 2 A
Maximum switching voltage 36V
Hint:
Binary inputs are not galvanically isolated.
Please see detail about wiring and description at chapter IL-NT BIO8 Hybrid binary input/output
module.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp intelilite nt amf20 and is the answer not in the manual?

ComAp intelilite nt amf20 Specifications

General IconGeneral
BrandComAp
Modelintelilite nt amf20
CategoryController
LanguageEnglish

Related product manuals