Page #87 background image
InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 87
IL-NT-AMF-2.2-Reference Guide.pdf
*Timer1..2Duration
Duration of Timer output is active.
Step: 1 min
Range: 1 1440 s
Test Period [d]
After the given value of Test Period setpoint expires, the engine is started and is running as long as
the value of Test Duration setpoint. Test Period starts counting always when the engine is stopped.
Range: 0 240 days
^ Available only in AMF20.
Test Duration [min]
Time interval, when engine is running after expiring the Test Period setpoint.
Range: 0 240 minutes
^ Available only in AMF20.
Hint:
This function does not work till both setpoints (Test Period and Test Duration) are set to non-zero
values.
Sensors Spec
AI1, AI2, AI3 Calibration […]
Calibrating constant to adjust the measured value of IL analog inputs. Physical dimension
of calibrating constant is corresponding to Analog input.
Step: 1
Range: -1000 +1000
Hint:
Calibration constants have to be adjusted when measured value is near the alarm level.
User curves can be defined by LiteEdit software.
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet Bridge are connected to the controller, the controller can send SMS
messages and/or emails at the moment when a new alarm appears in the Alarmlist. The message will
contain a copy of the Alarmlist.
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg the levels
of alarms to be announced (red/yellow/both) and also enter a valid GSM phone number and/or e-mail
address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to set either a GSM
number or e-mail at both setpoints.
The list of all supported terminals shows the table below:
Terminal
Active alarm
sms
Active event
sms
Active alarm
email
Active event
email
IB-Lite
N/A
N/A
yes
yes
IB-NT
N/A
N/A
yes
yes*
IL-NT-GPRS
yes
yes
Not
supported
Not
supported
*since IB-NT 2.2.0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp intelilite nt amf20 and is the answer not in the manual?

ComAp intelilite nt amf20 Specifications

General IconGeneral
BrandComAp
Modelintelilite nt amf20
CategoryController
LanguageEnglish

Related product manuals