Engine Params
Starting RPM [%]
“Firing” speed when IL controller stops cranking (starter goes OFF).
Step: 1% of nominal RPM
Range: 5 – 50 %
Starting Oil P [Bar]
When reached controller stops cranking (starter goes OFF).
Step: 0,1 bar
Range: 0,0 – 10,0
Hint:
There are three conditions for stop cranking: RPM > Starting RPM, Oil Pressure > Starting Oil P and
D+ (when enabled) => 80% of battery voltage. Starter goes off when any of these conditions is valid.
Prestart Time [s]
Time of closing of the Prestart output prior to the engine start.
Set to zero if you want to leave the output Prestart open.
Step: 1s
Range: 0 – 600 s
MaxCrank Time [s]
Maximum time limit of cranking.
Step: 1s
Range: 1 – 255 s
CrnkFail Pause [s]
Pause between Crank Attempts.
Step: 1s
Range: 5 – 60 s
Crank Attempts [-]
Max number of Crank Attempts.
Step: 1
Range: 1 – 10
Idle Time [s]
Idle time delay starts when RPM exceeds Starting RPM. Start fail is detected when during Idle state
RPM decreases below 2.
During the Idle time timer running the binary output Idle/Nominal is opened when it elapses the
Idle/Nominal output closes. Binary output Idle/Nominal opens during Cooling period again.
Step: 1 s
Range: 0 – 600 s