Prior to the dispenser reaching its preset amount, the solenoids are
switched to give a low flow rate. The “preset cut-off” sets the amount (in
litres), prior to the preset amount being attained, at which the solenoids will
switch to a low flow rate.
With the value set to 0.00, the default values are used. These are:
LPG 0.75
Oil 0.05
Other products 0.32
The Preset Cut-off is calculated as follows:
[Price per Litre] X [over-run (displayed as a dollar value)] + default value as
above.
Example:
Price per Litre = $0.96
Dollar amount of fuel required = $20.00
After delivery price display shows: $20.01 ($0.01 is the over-run dollar
value)
New preset = (0.96 x 0.01) + 0.32 (Other Products) = 0.3296
0.3296 rounded up = 0.33
New preset cut-off to be entered is 0.33.
Setting the Pre-Set Cut-Off
Refer to C4000 Set-Up K Factor Switch Settings (see page 21) The Price
display shows 'PCut' and the volume display shows 'PCX.XX'. The range is
from 0.01 to 9.99 litres.
Further Settings Available on the 'K' Factor Switch
The following configurations (K-Factor) switch settings are only available for
CNG dispensers, LPG dispensers, or bulk meter registers. As they are
reasonably uncommon, they have not been included in sequence with the
four more common settings.
These 'uncommon' settings are:
Density Factor 'dSF' - CNG (needs appropriate software)
Temperature'E'- LPG (with compensation) – Bulkmeter
ACV Valve Flow rate 'FLO' - Bulkmeter
L Cut 'L' - Bulkmeter
H Cut'H' - Bulkmeter
F Cut 'F' - Bulkmeter
Specific Density Calibration 'LP6' - LPG (with compensation and with
densometer).