Page #119 background image
6-23
VLT is a registered Danfoss trademark
Figure 6-15. D2 IGBT Modules (2 of 3)
Retaining screws
(shown removed)
(Step 8)
IGBT bus bar assembly BB29
(Steps 7 & 10)
IGBT module
IGBT module
Retaining screws
(Step 11)
Intermediate IGBT output bus bar BB30
(Step 12)
7. Remove 4 (10mm) retaining nuts at top of IGBT
bus bar assy.
8. Remove 12 retaining screws (6 on each module)
on upper portion of IGBT modules. These screws
also attach the snubber capacitors to the IGBT
modules (see Figure 6-15, 1 of 3 for snubber
capacitor location). Remove the snubber
capacitors.
9. Remove 10mm retaining nut from IGBT bus bar
assy.
10. Remove IGBT bus bar assy.
Retaining nut
(Step 7)
Retaining nut
(Step 12)
11. At bottom end of IGBT module, remove 12
retaining screws (4 each for U, V, and W
intermediate IGBT output bus bars).
12. Remove retaining nut (8mm) from 3 intermediate
IGBT output bus bars. Remove intermediate IGBT
output bus bars.
CONTINUED ON NEXT PAGE
Retaining nut
(Step 9)
BB31
BB30

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000-P and is the answer not in the manual?

Danfoss VLT 5000-P Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000-P
CategoryDC Drives
LanguageEnglish

Related product manuals