EasyManuals Logo
Home>Danfoss>DC Drives>VLT 5000-P

Danfoss VLT 5000-P User Manual

Danfoss VLT 5000-P
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
6-3
VLT is a registered Danfoss trademark
6.5 Gate Drive Card
1. Disconnect cables from connectors on gate drive
card MK102, MK103, MK104, MK106, and, if unit
has extended brake option, MK105, and, for 380-
500 V units with an RFI filter, MK101.
2. Remove gate driver card by removing 6 mounting
screws (T25 Torx) from standoffs.
Reinstall in reverse order of this procedure. Tighten mounting
screws to 20 in-lbs (2.25 Nm).
6.6 Soft Charge Card
1. Remove control card/power card mounting plate
in accordance with procedure.
2. Remove 2 retaining nuts from soft charge card
assembly (10mm).
3. Slide assembly part way out to access cable
connectors on card.
4. Disconnect MK1, MK2, MK3, and MK4.
5. Remove soft charge card assembly.
Reinstall by aligning soft charge card with fastening clips on
the side of the chassis. Reattach connectors. Slide into place
and tighten mounting screws to 35 in-lbs (4 Nm).
MK1
MK2
MK4
MK3
Mounting screw
(Step 2)
Figure 6-4. Soft Charge Card Assy
Figure 6-3. Gate Drive Card
MK102 (U) MK103 (V) MK104 (W)MK105
brake option
MK106
MK101 (RFI filter)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000-P and is the answer not in the manual?

Danfoss VLT 5000-P Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000-P
CategoryDC Drives
LanguageEnglish

Related product manuals