4.3 Events
4.3.1 Genset controller events
Events, Events
Description Notes
Mains fail Mains failure condition.
Peak shaving active
Peak shaving cuts the peak of the mains consumption by paralleling the generator
to the mains.
G volt/freq OK delay expired Diesel generator V/Hz OK.
Access lock Binary input access lock activated.
Lamp test Lamp test in progress.
Battery test active Battery test in progress.
Mains U OK timer has expired The timer for mains voltage OK has expired.
Mains F OK timer has expired The timer for mains frequency OK has expired.
Test type simple selected Selection of test type: Simple test.
Test type load selected Selection of test type: Load test.
Test type full selected Selection of test type: Full test.
BB voltage OK Busbar voltage.
G volt/freq OK Generator frequency and voltage are within range.
Ack. all alarms active Acknowledge all active alarms.
Mode shift activated Mode shift between a running mode and AMF (Automatic Mains Failure) activated.
Mode shift deactivated
Mode shift between a running mode and AMF (Automatic Mains Failure)
deactivated.
GOV up activated Speed governor increase activated.
GOV down activated Speed governor decrease activated.
AVR up activated AVR (voltage control) increase activated.
AVR down activated AVR (voltage control) decrease activated.
CBE activated Activate Close Before Excitation function.
CBE deactivated Deactivate Close Before Excitation function.
Inductive reference selected Inductive cos phi reference.
Capacitive reference selected Capacitive cos phi reference.
Dynamic sync selected Dynamic synchronisation method selected.
Static sync selected Static synchronisation method selected.
Power offset [1-3] activated Power reference offset activated.
Cos phi offset [1-3] activated Cos phi reference offset activated.
Analogue offset set [1-4] active The analogue offset set follow the activated nominal settings (1, 2, 3 and 4).
Mains sync. inhibit activated
The mains breaker sync. inhibit function is activated (this does not necessarily
inhibit the synchronisation of the mains breaker).
Mains sync. inhibited The mains breaker is in fact inhibited.
Max ventilation activated True when maximum ventilation is activated.
Max ventilation deactivated True when maximum ventilation is deactivated.
Ethernet ready Ethernet is ready for read/write.
Application note 4189341276B EN Page 17 of 50