Output, Command - Plant
Description Notes
Select application [1-4] Power management: Select the application from the controller.
Output, Command - Power management
Description Notes
Set to local start Select local start in a power management application.
Set to remote start Select remote start in a power management application.
Run my ID - constant Runs the connected mains (constant)
Run my ID - activate Runs the connected mains (one shot)
Run one mains Only one mains breaker is closed at the time.
Run all mains All mains breakers are closed at the time.
Update mode local Running mode update for the local controller.
Update mode on all
The running mode for all controllers in the power management system is updated
to the selected mode.
Store common settings See Handling settings for sections in Option G5 Power management.
Auto start/stop ON = Start, OFF = Stop.
Autoswitch off Auto-switch is not enabled.
Autoswitch static Auto-switch enabled for static section.
Autoswitch dynamic Auto-switch enabled for dynamic section.
Autoswitch all Auto-switch enabled for all sections.
Act. TB deload Activate tie breaker de-load (only in semi-auto mode).
Alternative start Activates alternative start.
TB power capacity - direct close See Tie breaker configuration in Option G5 Power management.
TB ignore LED/button Disables the TB LED on the controller when mains is without tie breaker.
Assume all BTB POS fdb OFF in case of pos
fail or ID missing
Fault handling procedure.
5.1.3 Bus tie breaker controller commands
Commands for BTB
Description
Notes
Semi-Auto mode Semi-auto running mode.
Auto mode Auto running mode.
Block mode Block running mode.
Lamp test Activate lamp test (LEDs on display).
Ack. all alarms Acknowledge all alarms.
Set clock to 4 am Set the controller clock to 04h00.
Switch log to print Switch between event, alarm and battery log to print.
Print log Print output.
Print status Print output.
Set parameter [1-4] Choose the parameter set for nominal settings.
BTB close inhibit Prevents the BTB from closing.
Application note 4189341276B EN Page 38 of 50

Table of Contents

Other manuals for Deif AGC-4 Mk II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deif AGC-4 Mk II and is the answer not in the manual?

Deif AGC-4 Mk II Specifications

General IconGeneral
BrandDeif
ModelAGC-4 Mk II
CategoryController
LanguageEnglish

Related product manuals