Table 2. AC power specifications (continued)
Requirement Description
Power factor 0.98 min at full load, low voltage
Heat dissipation (operating maximum) 1.69 x 10
6
J/hr (1604 Btu/hr) max
In-rush current 37.6 A max for ½ line cycle "cold," per line cord at 240 V ac
38 A max for ½ line cycle "hot," per line cord at 240 V ac
Startup surge current 29 A max, prior to HVDC regulation, during startup or after AC interruption
AC protection Flex Optimus, 16 A fuse on the line side of each power supply, both phases
Acbel Optimus, 15A fuse on the line side of each power supply, both phases
AC inlet type IEC320-C14 appliance coupler, per power supply
Ride-through time 12 ms min
Current sharing ± 5% of full load, between power supplies
Dimensions and weight
Table 3. Dimensions and weight
Dimensions Vertical size Weight (see note)
Height: 3.40 in (8.64 cm)
2 NEMA units 80lbs (36.3 kg)Width: 17.50 in (44.45 cm)
Depth: 30.5" in (77.5 cm)
Note: The weight does not include mounting rails. Allow 2.3-4.5 kg (5-10 lb) for a rail set. The weights listed in this table do
n
ot describe enclosures with solid state disk drives with Flash memory (called Flash or SSD drives). These Flash drive modules
weigh 20.8 ounces (1.3 lb) each.
Specifications 7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dell Data Domain DD6300 and is the answer not in the manual?

Dell Data Domain DD6300 Specifications

General IconGeneral
BrandDell
ModelData Domain DD6300
CategoryNetwork Hardware
LanguageEnglish

Related product manuals