Two-Post Rack Installation 31
Wide-Hole Spacing Racks
Racks with wide-hole spacing have an alternating pattern of two holes per rack unit with center-to-center
hole spacing (beginning at the top hole of a 1-U space) of 31.7 mm and 12.7 mm (1.25 inches and 0.5 inch)
for the front and back vertical columns of holes (see Figure 2-3).
Figure 2-3. Two-Post, Open-Frame Relay Rack Wide-Hole Spacing
To mark the rack, perform the following steps:
1
Place a mark on the rack's front vertical rails where you want to locate the bottom of the system you are
installing in the two-post rack.
The bottom of each 1-U space is at the middle of the narrowest metal area between holes.
NOTE: If your rack has wide-hole spacing, go to step 3.
2
Place a mark 44 mm (1.75 inches) above the original mark you made (or count up three holes in a rack
with universal-hole spacing) (see Figure 2-2).
Each 1 U (44 mm, or 1.75 inches) of vertical space on a rack with universal-hole spacing has three holes
with center-to-center spacing between holes (beginning at the top of a 1-U space) of 15.9 mm,
15.9 mm, and 12.7 mm (0.625 inch, 0.625 inch, and 0.5 inch) (see Figure 2-2).
NOTE: If your rack has universal-hole spacing, you have completed the procedure for marking the rack.
3
Place a mark 44 mm (1.75 inches) above the original mark you made (or count up to the next hole in
the rack with wide-hole spacing (see Figure 2-3).
Each 1 U (44 mm, or 1.75 inches) of vertical space on a rack with wide-hole spacing has two holes with
center-to-center spacing between holes (beginning at the top of a 1-U space) of 31.7 mm (1.25 inches)
(see Figure 2-3).
1 U (44 mm or 1.75 inches)
12.7 mm (0.5 inch)
31.7 mm (1.25 inches)

Table of Contents

Other manuals for Dell PowerEdge 1950

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dell PowerEdge 1950 and is the answer not in the manual?

Dell PowerEdge 1950 Specifications

General IconGeneral
Processor Sockets2
ChipsetIntel 5000X
Memory Slots8 DIMM slots
NetworkDual embedded Broadcom NetXtreme II 5708 Gigabit Ethernet
Form Factor1U Rack
ProcessorIntel Xeon 5100, 5300 series
MemoryUp to 32GB DDR2
StorageSAS or SATA
Drive BaysTwo 3.5" SAS or SATA drives or Four 2.5" SAS or SATA drives
RAID ControllerPERC 5/i, PERC 6/i
Power Supply670W redundant power supply (optional)
Operating System SupportMicrosoft Windows Server, Red Hat Linux, SUSE Linux

Related product manuals