Page 13 -1
Effective 10/02 IL17562BH04
13.2.1 General Description
The purpose of the Quick Release Drawout Case is to remove the
relay from service without disconnecting the wires. The MP-3000
Drawout Relay maintains the same electrical and operating specifica-
tions as the standard MP-3000. Specifications for the Drawout
connectors are shown in table 13.2.
Table 13.2 Drawout connector Specifications
Make/Break Rating 10 A @ 240 Vac nominal
0.25 A @ 280 Vdc maximum
Terminal Wire Gauge No. 14 to No. 10 AWG
Screw Torque Requirements 18 inch-pounds
The MP-3000 Drawout consists of two assemblies: an inner chassis,
and an outer chassis (see Figure 13.1). The outer chassis consists of
an aluminum housing with terminal blocks, a molded plastic flange
with quick-release actuators, and a locking mechanism.
Fig. 13.1 MP-3000 Drawout Relay
13.2.1 Self-Shorting Ct Connections
The Drawout terminal blocks features self-shorting, or short-before-
break set of contacts, for Ct connections that maintain circuit
continuity when the device is removed. These self-shorting contacts
will prevent damaging voltages from existing across the current
transformer windings.
An extra set of self-shorting terminals are provided that may be used
to keep the motor running while the relay is out of its case or to
provide a No Protection Alarm (see Section 13.5 for more information).
13.3 Installation
NOTICE
THE FOLLOWING MATERIAL SUPPLEMENTS INSTALLATION
INFORMATION IN SECTIONS 6.1.1, 6.1.2, AND 6.1.3, AND
FIGURES 6.1 AND 6.3. REFER TO THESE SECTIONS FIRST.
13.3.1 Panel Preparation
The Drawout case uses the same Panel Cutout as the fixed mount
MP-3000, IQ1000II and IQ1000. When mounting the Drawout Case in
a panel, it is necessary to prepare a cutout for the device per Figure
13.2. If a standard IQ cutout exists, no additional panel setup is
required; the Drawout will mount securely in an existing 6-hole or
10-hole cutout.
13.3.2 MP-3000 Drawout Relay Parts List
Before mounting the Drawout Relay, check the contents of the box for
the parts listed in Table 13.3 and shown in Figure 13.3.
SECTION 13—DRAWOUT CASE OPTION FOR THE
MP-3000 MOTOR PROTECTION RELAY
CAUTION
COMPLETELY READ AND UNDERSTAND THIS INSTRUCTION
BOOK BEFORE ATTEMPTING INSTALLATION, OPERATION OR
APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY
QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM
ANY WORK ASSOCIATED WITH THE EQUIPMENT. ANY WIRING
INSTRUCTIONS PRESENTED IN EITHER DOCUMENT MUST BE
FOLLOWED CLOSELY. FAILURE TO DO SO COULD CAUSE
PERMANENT EQUIPMENT DAMAGE.
13.1 Introduction
This section describes the Drawout Case option for the MP-3000
Motor Protection Relay.
The basic operation of the MP-3000 relay is applicable to all styles of
the drawout case. Table 13.1 lists the Drawout Case versions.
Table 13.1 Ordering Information
Description Cat. No. Style No.
MP-3001 66D2033G11
MP-3002 66D2033G12
MP-3101 66D2033G13
MP-3102 66D2033G14
MP-3001-IC 66D2029G21
MP-3002-IC 66D2029G22
MP-3101-IC 66D2029G23
MP3102-IC 66D2029G24
MP-3001-OC 66D2035G11
MP-3000 Drawout Relay, 5 A,
no communications
MP-3000 Drawout Relay, 5 A,
built in INCOM communications
MP-3000 Drawout Relay, 1 A,
no communications
MP-3000 Drawout Relay, 1 A,
built in INCOM communications
MP-3000 Drawout
Inner Chassis
5 A, no communications
5 A, INCOM communications
1A, no communications
1A, INCOM communications
MP-3000 Drawout Outer Case