Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 79
Figure 40. Terminal Blocks TB1, TB2, and TB3 Connector Assignments
UPS
Building Alarm 3
Building Alarm 3 Return
Building Alarm 4
Building Alarm 5
Building Alarm 4 Return
Building Alarm 5 Return
NOTE All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either
normally-open or normally-closed contacts. All control wiring and relay and switch contacts are customer-supplied.
NOTE The building alarms can be programmed to display the alarm functional name.
NOTE A jumper wire must be connected between pins 1 and2on TB1, if the normally-closed REPO contact is not used.
1
10
1
10
TB1
TB2
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
REPO NO
REPO NC
REPO Return
Battery Aux
Battery Aux Common
Battery Shunt Trip +
+
Battery Shunt Trip
UPS
1
10
TB3
Building Alarm 1 Return
Building Alarm 1
Building Alarm 2 Return
Building Alarm 2
Alarm Relay Common
Pull Chain
Pull Chain Common
REPO Return
Output Contactor K3 NC Aux Common
Output Contactor K3 NC Aux
UPS System Installation

Table of Contents

Other manuals for Eaton Power Xpert 9395P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Power Xpert 9395P and is the answer not in the manual?

Eaton Power Xpert 9395P Specifications

General IconGeneral
BrandEaton
ModelPower Xpert 9395P
CategoryUPS
LanguageEnglish

Related product manuals