210 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
99..22 PPeerrffoorrmmiinngg PPrreevveennttiivvee MMaaiinntteennaannccee
The UPS system requires very little preventive maintenance. However, the system should be inspected
periodically to verify that the units are operating normally and that the batteries are in good condition.
99..22..11 DDAAIILLYY MMaaiinntteennaannccee
Perform the following steps daily:
1. Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the
unit.
2. Ensure the air intakes (vents on the front door and panel) and the exhaust opening (on top of the UPS
cabinet) are not blocked.
3. Ensure the operating environment is within the parameters specified in paragraph
3.2.2 Environmental and Installation Considerations and Chapter 10 Product Specifications.
4. Ensure the UPS is in Online mode (Online status indicator is illuminated). If an alarm lamp is illuminated or
the Online status indicator is not illuminated, contact an Eaton service representative.
99..22..22 MMOONNTTHHLLYY MMaaiinntteennaannccee
Perform the following steps monthly:
1. Monitor system parameters as described in paragraph 7.2 Using the LCD Control Panel.
2. Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See
Figure 130 and Figure 131 or Figure 132 for filter locations, and Table 40 for filter sizes. Contact an Eaton
service representative for replacement filters. To remove the filters:
Table 40. UPS Filter Sizes
Filter Location Size
Bottom Left ISBM Section Air Filters (Continuous Static Switch only)
12" x 20" x 0.25"
Bottom Right ISBM Section Air Filters (Continuous Static Switch only)
12" x 20" x 0.25"
Middle Right ISBM Section Air Filter (Continuous Static Switch only)
20" x 6.3" x 0.25"
UPM Section Air Filters 20" x 44" x 0.25"
Verify washed filters are thoroughly dry before reinstalling.
Verify washed filters are thoroughly dry before reinstalling.
a. Remove one top screw and two bottom screws securing each UPM front panel (see Figure 18). Lift
each panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
b. Remove one top screw and two bottom screws securing the ISBM left front panel (see Figure 17). Lift
the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
c. If the UPS is a continuous static switch configuration, unfasten the front door latch and swing the door
open (see Figure 16).
d. Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters from
the cabinet.
UPS Maintenance