101
FOUNDATION fieldbus
The FISCO standard applies to the FM, CSA, IECEx, and ATEX
certifications.
Intrinsically Safe FISCO
Intrinsically Safe Non-FISCO
International Certification IECEx
Certification No.: IECEx BVS 10.0094
Ex ia [ia Ga] [ia Da IIIC] IIC T4 Gb (-10°C ≤ Ta
≤ +50°C)
HART Intrinsically Safe electrical parameters
Input Parameters
Output Parameters
F
OUNDATION fieldbus
Intrinsically Safe FISCO
Intrinsically Safe Non-FISCO
North American
Certifications
Factory Mutual (FM)
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D and
Class I
, Zone 0, AEx ia IIC T4 (Ta = 50°C) hazardous locations when
connected as indicated in the control drawing 00475-1130. See the
control drawing for input and output parameters.
Canadian Standards Association (CSA)
Intrinsically Safe for use in Class I, Ex ia [ia Ga] [ia Da IIIC] IIC T4 Gb
Output Parameters
U
0
= 1.9 Volt DC
I
0
= 32 μA
U
iIIC
= 17.5 Volt DC I
iIIC
= 215 mA P
iIIC
= 1.9 Watt
U
iIIB
= 17.5 Volt DC I
iIIB
= 380 mA P
iIIB
= 5.3 Watt
U
0
= 1.9 Volt DC I
0
= 32 µA
U
i
= 30 Volt DC I
i
= 380 mA P
i
= 1.3 Watt
U
0
= 1.9 Volt DC I
0
= 32 µA
L
i
= 0 C
i
= 0
U
i
= 30 Volt DC
I
i
= 200 mA
P
i
= 1.0 Watt
L
i
= 0
C
i
= 0
U
0
= 1.9 Volt DC
I
0
= 32 μA
U
iIIC
= 17.5 Volt DC I
iIIC
= 215 mA P
iIIC
= 1.9 Watt
U
iIIB
= 17.5 Volt DC I
iIIB
= 380 mA P
iIIB
= 5.3 Watt
U
0
= 1.9 Volt DC I
0
= 32 µA
U
i
= 30 Volt DC I
i
= 380 mA P
i
= 1.3 Watt
U
0
= 1.9 Volt DC I
0
= 32 µA