EasyManuals Logo
Home>Emerson>I/O Systems>ControlWave

Emerson ControlWave User Manual

Emerson ControlWave
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
ControlWave Instruction Manual (CI-ControlWave)
5-14 Service & Troubleshooting Revised Nov-2010
Module /
Board
LED Name LED Color Function and Location
SCB CR4 – ENET Port 2 Red/Green ON RED = Data Collision (Left – see Figure 5-
11.)
SCB CR4 – ENET Port 2 Red/Green ON GREEN = Receiving data (Left – see
Figure 5-11.)
SCB CR4 – ENET Port 2 Red/Green ON RED = Transmitting data (Right – see
Figure 5-11.)
SCB CR4 – ENET Port 2 Red/Green ON GREEN = Link O.K. (Right – see Figure 5-
11.)
SCB CR5 – ENET Port 3 Red/Green ON RED = Data Collision (Left – see Figure 5-
11.)
SCB CR5 – ENET Port 3 Red/Green ON GREEN = Receiving data (Left – see
Figure 5-11.)
SCB CR5 – ENET Port 3 Red/Green ON RED = Transmitting data (Right – see
Figure 5-11.)
SCB CR5 – ENET Port 3 Red/Green ON GREEN = Link O.K. (Right – see Figure 5-
11.)
CPU PORT 80 DISPLAY Red LEDs LED Matrix displays status codes. See Figure
5-11. See Table 5-3 & 5-4.
AI AI Board Status Red/Green ON RED = Fail state/ board not recognized
ON GREEN = Normal state. See Figure 5-12
AI Range (16 LEDs – one per
point)
Red LED ON = AI over-range or AI under-range
condition. See Figure 5-12
AI Range (16 LEDs – one per
point)
Green LED ON = AI in range. See Figure 5-12
AO AO Board status fail Red LED ON = AO board fail state / board not
recognized. See Figure 5-13.
AO AO Board status pass Green LED ON = AO board normal or O.K. state.
Figure 5-13.
DI DI Board status Red/Green ON RED = DI board fail state; board not
recognized.
ON GREEN = DI board normal state. See
Figure 5-14.
DI DI board inputs (32 LEDs – 1
per point)
Red LED ON = Input is present.
LED OFF = Input is not present. See Figure 5-
14.
DO DO Board status Red/Green ON RED = DO board fail state; board not
recognized.
ON GREEN = DO board normal state. See
Figure 5-15.
DO DO board outputs (32 LEDs –
1 per point)
Red LED ON = Output is ON. See Figure 5-15.
UDI UDI Board Status Fail Red LED ON = UDI board fail state/board not
recognized. See Figure 5-16.
UDI UDI Board Status Pass Green LED ON = UDI board normal or O.K. state.
See Figure 5-16.
UDI UDI Input (12 LEDs – 1 per Red LED ON = UDI input activity.

Table of Contents